섬식 지하철역사내 화재시 연기제어에 관한 수치해석적 연구

A Numerical Study on the Smoke Control in Center-Platform Type Subway Station Fires

  • 발행 : 2007.06.30

초록

In this study, numerical simulations were carried out to analyze the effect of the smoke extraction system and fire shutters in subway station fires using FDS 4.0. Subway station used in the experiment was 145 m long. Simulation results are validated by comparing with experimental results. Simulation results showed good agreement with experimental results within $10^{\circ}C$. 10 MW polystyrene was used as a fuel in the numerical prediction. Numerical predictions were performed in the center-platform type subway station in case of a kiosk fire. Temperature and CO concentration were lowered by the operation of smoke extraction system. But, the operation of fire shutters had little effect on temperature and CO concentration in the platform level.

키워드

참고문헌

  1. Hong, WH. (2004). 'The progress and controlling situation of Daegu subway fire disaster,' 6th Asia-Oceania Symposium on Fire Science and Technology, Dague, Korea, pp.28-46
  2. Modic, J. (2003). 'Fire simulation in road tunnels,' Tunnelling and Underground Space, Vol. 18, No.5, pp.525-530 https://doi.org/10.1016/S0886-7798(03)00069-5
  3. Gao, P. Z., Liu, S. L. Chow, W. K. and Fong, N. K. (2004). 'Large eddy simulations for studying tunnel smoke ventilation,' Tunnelling and Underground Space, Vol. 19 No. 6, pp.577-586 https://doi.org/10.1016/j.tust.2004.01.005
  4. Vauquelin, O. and Wu, Y. (2006). 'Influence of tunnel width on longitudinal smoke control,' Fire Safety Journal, Vol. 41 No. 6, pp.420-426 https://doi.org/10.1016/j.firesaf.2006.02.007
  5. Moriyama S., Hasemi Y., Okazawa N., Nam DG. and Ding W. (2006). 'Smoke Movement Tests in Subway Stations Actually in Service Smoke Movement Characteristics in Center Platform Stations in the Early Stage of a Fire,' Bulletin of Japan Association for Fire Science and Engineering, Vol. 56 pp.23-35(in Japanese)
  6. McGrattan, K.B. (2006). Fire dynamics simulator (version 4)-Technical reference guide, NIST