Development of a Ubiquitous Sensor for Monitoring Insulators and Lightning Arresters

애자/피뢰기 모니터링을 위한 유비쿼터스 센서 개발

  • 길경석 (한국해양대학교 전기전자공학부) ;
  • 류길수 (한국해양대학교 IT공학부) ;
  • 송재용 (국립과학수사연구소) ;
  • 김일권 (한국해양대학교 전기전자공학부) ;
  • 박대원 (한국해양대학교 전기전자공학부) ;
  • 최수연 (한국해양대학교 전기전자공학부)
  • Published : 2007.04.30

Abstract

In this study, a ubiquitous sensor for condition monitoring of insulators and lightning arresters installed in power distribution lines and electric traction vehicles is presented. The sensor consists of two parts; a leakage current measurement and a lightning surge detection. Measured data are transmitted to a supervisory computer through ZigBee protocol based on IEEE 802.15.4. To detect leakage current, a window type Mn-ZCT is used and a low-noise amplifier with a gain of 60dB is designed, and this can measure leakage current in ranges of $100{\mu}A{\sim}5mA$. A sample-hold (S/H) and a Rogowski coil are injected to analyze the magnitude of surge current in ranges from 100A to 10kA with $8/20{\mu}s$-waveform.

Keywords

References

  1. S. Tominaga, Y. Shibuya, T. Fujiwara, M. Imataki, T. Nitta, 1980, 'Stability and Long Term Degradation of Metal Oxide Surge Arresters', IEEE Trans. on PAS., vol.PAS-99, no.4, pp.1548-1556 https://doi.org/10.1109/TPAS.1980.319580
  2. Y. Yamashita, S. Yoshikado, 1999, 'Evaluation of factors in the degradation of ZnO varistor', Trans. on IEEJ, vol.119-B, no.6, pp.652-657
  3. Peter Hasse1, 2004, Overvoltage protection of low-voltage systems, The Institution of Electrical Engineers, p.358
  4. R. A. Sargent et al., 1992, 'Effects of Multiple Impulse Currents on the Microstructure and Electrical Properties of Metal-oxide Varistors', IEEE Transaction on Electrical Insulation, Vol.27, No.3, pp.586-592 https://doi.org/10.1109/14.142723
  5. 길경석, 한주섭, 한문섭, 2004, '철도용 피뢰기의 열화진전에 관한 연구', 한국철도학회논문집, 제7권, 제4호, pp.307-311
  6. T. K. Gupta, 1990, 'Application of zinc oxide varistors', Journal of the American Ceramic Society, Vol.73, No.7, pp.1817-1840 https://doi.org/10.1111/j.1151-2916.1990.tb05232.x
  7. IEEE 802.15.4, 2004, Standard for Telecommunications and Information Exchange Between Systems-LAN/MAN Specific Requirements - Part 15: Wireless Medium Access Control (MAC) and Physical Layer (PHY) Specifications for Low Rate Wireless Personal Area Networks (WPAN)
  8. J. Lundquist et al., 1990, 'New Method for Measurement of the Resistive Leakage Currents of Metal-Oxide Surge Arrester in Service', IEEE Trans. on Power Delivery, Vol. 5, No. 4, pp.1811-1822 https://doi.org/10.1109/61.103677
  9. K. Eda, A. Iga, M. Matsuoka, 1980, 'Degradation Mechanism of Non-ohmic Zinc Oxide Ceramics, Journal of Applied Physics', Vol. 51, No. 5, pp.2678-2684 https://doi.org/10.1063/1.327927
  10. Ray W.F. and Davis R.M., 1997, 'Developments in Rogowski current transducers', EPE Conf. Proc., Trondheim, Vol. 3, pp.308-312
  11. Ray W. F. and Davis R. M., 1993, 'Wide bandwidth Rogowski current transducers : Part 1 - The Rogowski coil', EPC journal, Vol. 3, No.1, pp.51-59 https://doi.org/10.1080/09398368.1993.11463312
  12. Ray W. F., 1993, 'wide bandwidth Rogowski current transducers: Part 2 - The integrator', EPE journal, Vol.3, No.2, pp.116-122