The Assessment of Fire Suppression Capability of Water-Mist System for Machinery Engine Room

선박기관구역 미분무수 소화설비 화재진압 성능 평가

  • 최병일 (한국기계연구원 에너지기계연구센터) ;
  • 한용식 (한국기계연구원 에너지기계연구센터) ;
  • 오창보 (한국기계연구원 에너지기계연구센터) ;
  • 김명배 (한국기계연구원 에너지기계연구센터) ;
  • 김창 ((주)WIN)
  • Published : 2007.06.30

Abstract

Full scale fire suppression test by water mist system were performed in machinery engine room ($20m{\times}15m{\times}10m$) according to IMO MSC/circ. 1165. The K-factor and operating pressure were 2.4 and 80 bar respectively. To assess the prediction capability of numerical simulation, FDS simulation was performed at the same operating condition with the full scale experiment. It was found that FDS simulation had the limitation for the fire extinguishing time prediction but was able to predict the spatial temperature distribution.

IMO MSC/circ. 1165 규정에 따라 미분무수를 이용한 선박 기관구역($20m{\times}15m{\times}10m$)에서의 실물화재 소화실험을 수행하였다. K-factor 2.4인 노즐을 사용하였으며 작동압력은 80 bar이다. 미분무수의 화재진압 특성을 수치적으로 예측하기 위하여 FDS를 사용하여 실험과 같은 조건에서의 전산시뮬레이션을 수행하였다. 전산 시뮬레이션 결과 화재 전산 시뮬레이션 기법이 화재소화시간 예측에는 한계를 가지나, IMO MSC/circ. 1165 규정의 공간 내 온도분포 제어 성능의 예측을 위해서 유용하게 활용될 수 있음을 보였다.

Keywords

References

  1. NFPA 750, Standard on Water Mist Fire Protection Systems, 2000 ed., NFPA
  2. SFPE Handbook of Fire Protection Engineering 3rd edition, NFPA(2002)
  3. G. Santos, 'Water Mist Technology for Under Ground Transportation Systems', International Water Mist Conference(2003)
  4. 한용식, 최병일, 김명배, '변압기실 화재에 대한 미분무수 소화시스템의 적용 - 소화특성을 중심으로(Part1)', 한국화재소방학회논문지, Vol. 19, No. 4, pp.32-36(2005)
  5. 최병일, 한용식, 김명배, '변압기실 화재에 대한 미분무수 소화시스템의 적용 - 냉각특성을 중심으로(Part2)', 한국화재소방학회논문지, Vol. 19, No. 4, pp.37-41(2005)
  6. Imo Msc/circ. 1165, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-rooms(2005)
  7. 지역산업기술개발사업 중간보고서, '선박용 첨단 소화시스템의 소화성능평가 및 설계해석기술개발', 산업자원부(2006)
  8. K.B. McGrattan, 'Fire Dynamics Simulator (Version 4), Technical Reference Guide', NIST Special Publication 1018, National Institute of Standards and Technology, Gaithersburg, Maryland, July(2004)
  9. K.B. McGrattan, 'Fire Dynamics Simulator (Version 4), User's Guide', NIST Special Publication 1019, National Institute of Standards and Technology, Gaithersburg, Maryland, July(2004)
  10. G.P. Forney and K.B. McGrattan, 'User's Guide for Smokeview Version 4', NIST Special Publication 1017, National Institute of Standards and Technology, Gaithersburg, Maryland, July(2004)
  11. G. Grant, J. Brenton, and D. Drysdale, 'Fire Suppression by Water Spray', Progress in Energy and Combustion Science, Vol. 26, pp.79-130(2000) https://doi.org/10.1016/S0360-1285(99)00012-X
  12. 노재성, 양승신, 김동현, 정우성, 장용준, 유홍선, '중저압 물분무를 이용한 객차내 화재진압에 관한 실험 및 수치해석적 연구', 한국철도학회논문집, Vol. 9, No. 3, pp.291-297(2006)
  13. S.C. Kim and H.S. Ryou, 'The Effect of Water Mist on Burning Rates of Pool Fire', Journal of Fire Sciences, Vol. 22, pp.305-323(2004) https://doi.org/10.1177/0734904104041796