Optimization of the Area Ratio of Regeneration to Dehumidification and Rotor Speed on the Condition of Low Regeneration Temperature

재생온도가 저온인 경우 제습로터의 재생부/제습부 면적비율과 회전속도 최적화

  • Published : 2007.07.10

Abstract

The desiccant rotor is the most essential component of desiccant cooling system, but its design relies on manufacturer's experience and principles are not yet clear in spite of a lot of theoretical/experimental work published. The mathematical modeling of desiccant rotor needs solution of coupled partial differential equations of heat and mass transfer. In this study, numerical program is developed and validated using a real desiccant rotor. The calculation results are in reasonable agreement with the experimental data and other available numerical results. Optimization of desiccant rotor on the condition of low regeneration temperature are investigated. The optimal rotor speed at which the process outlet humidity becomes minimized, shows same as that of the system optimization. Compared to high regeneration temperature, broad is the range of optimal speed of low regeneration temperature. Systematic analysis on the optimal area ratio of regeneration to dehumidification section has also been conducted.

Keywords

References

  1. Daou, K. Wang, R. Z. and Xia, Z. Z., 2006, Desiccant Cooling Air Conditioning : A Review, Renewable and Sustainable Energy Reviews, Vol. 10, pp. 55-77 https://doi.org/10.1016/j.rser.2004.09.010
  2. Jain, S. and Dhar, P. L., 1995, Evaluation of Solid Desiccant-based Evaporative Cooling Cycles for Typical Hot and Humid Climates, Int. J. Refrig., Vol. 18, pp. 287-296 https://doi.org/10.1016/0140-7007(95)00016-5
  3. Halliday, S. P., Beggs, C. B. and Sleigh, P. A., 2002, The use of solar desiccant cooling in the UK : a feasibility study, Appl. Thermal Engng., Vol. 22, pp. 1327-1338 https://doi.org/10.1016/S1359-4311(02)00052-2
  4. Dai, Y. J., Wang, R. Z., Zhang, H. F. and Yu, J. D., 2001, Use of desiccant cooling to improve the performance of vapour compression air conditioning, appl. Thermal. Engng., Vol. 21, pp. 1185-1205 https://doi.org/10.1016/S1359-4311(01)00002-3
  5. Mazzei, P., Minichiello, F. and Palma, D., 2002, Desiccant HVAC systems for commercial buildings, Appl. Thermal Engng., Vol. 22, pp. 545-560 https://doi.org/10.1016/S1359-4311(01)00096-5
  6. Henning, H.-M., Erpenbeck, T., Hindenburg, C. and Santamaria, I. S., 2001, The Potential of Solar Energy Use in Desiccant Cycles, Int. J. Refrig., Vol. 24, pp. 220-209 https://doi.org/10.1016/S0140-7007(00)00024-4
  7. Aristov, Yu. I., Tokarev, M. M., Gordeeva, L. G., Snytnikov, V. N. and Parmon, V. N., 1999, New composite sorbents for sorlordriven technology of fresh water production from atmosphere, Solar Energy, Vol. 66, pp. 165-168 https://doi.org/10.1016/S0038-092X(98)00110-8
  8. Liu, Y. F. and Wang, R. Z., 2003, Pore structure of new composite $SiO_2.\;xH_2O.\;yCaCl_2$ with Uptake of Water Air, Sci. China, Vol. 46, pp. 551-559 https://doi.org/10.1360/02ye0480
  9. Zheng, W. and Worek, W. M., 1993, Numerical simulation of combined heat and mass transfer processes in a rotary dehumidifier, Numerical Heat Transfer, A23, pp. 211-232
  10. Dai, Y.J., Wang, R. Z. and Zhang, H. F., 2001, Parameter analysis to improve rotary desiccant dehumidification using a mathematical model, Int. J. Therm. Sci., Vol. 40, pp. 400-408 https://doi.org/10.1016/S1290-0729(01)01224-8
  11. Sphaier, L. A. and Worek, W. M., 2004, Analysis of heat and mass transfer in porous sorbents used in rotary regenerators, Int. J. Heat Mass Transfer, Vol. 47, pp. 3415-3430 https://doi.org/10.1016/j.ijheatmasstransfer.2004.01.016
  12. Lee, G., Lee, D.-Y. and Kim, M. S., 2004, Development of a linearized model and verification of the exact solution for the analysis of a desiccant dehumidifier, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 16, pp. 811-819
  13. Zhang, L. Z. and Niu, J. L., 2002, performance comparisons of desiccant wheels for Air dehumidification and enthalpy recovery, Applied Thermal Engineering, Vol,22, pp. 1347-1367 https://doi.org/10.1016/S1359-4311(02)00050-9
  14. Lee, D.-Y., Lee, G. and Kim, M. S., 2007, A proposal for new definition of performance indices of a desiccant rotor, Korean Journal of Air-Conditioning and Refrigeration Engineering, submitted
  15. Chung, J. D., Lee, D.-Y. and Yoon, S. M., 2007, Design of desiccant cooling system for the individual household of apartment house using district heating, Proceedings of the SAREK 2007 Summer Annual Conference
  16. Brillhart, P. L., 1997, Evaluation of desiccant rotor matrices using an advanced fixed-bed test system, Ph. D. thesis, Univ. of Illinois at Chicago