DOI QR코드

DOI QR Code

복합 가속열화를 통한 배전용 고분자 피뢰기의 장기 열화특성 예측

Longterm Aging Characteristics of Distribution Polymer Housed Surge Arresters by Multistress Accelerated Aging

  • 김주용 (한국전력공사 전력연구원) ;
  • 권태호 (한국전력공사 전력연구원) ;
  • 박철배 (한국전력공사 전력연구원) ;
  • 김준일 (한국전력공사 전력연구원)
  • 발행 : 2007.08.01

초록

In this study accelerated aging test equipment was developed to simulate domestic weather condition for accelerated aging test of polymer housed distribution surge arresters. Polymer arresters were aged for 3,000 hours by this test equipment and chemical and electrical characteristics analysis of surge arresters were conducted after aging test. In addition, performance assessment of outdoor installed arresters for 3 years was conducted to compare aging effect between accelerated aging test and natural aging. Through this experiment it is verified that the capability of the proposed aging test for simulating natural aging and the housing material and disconnector of domestic polymer arresters can be deteriorated by the long time field operation.

키워드

참고문헌

  1. E. A. Cherney, 'Non-ceramic insulators for contaminated environments', IEEE Trans. on Power Apparatus and Environments', No. 1, PAS-100, p. 131, 1981 https://doi.org/10.1109/TPAS.1981.316895
  2. 송일근, 한재홍, 김주용, '배전용 폴리머애자의 신뢰성 평가 및 운용기준 제정', 최종보고서, 전력연구원, 2001
  3. IEC standard 60099-4, 'Metal-oxide surge arresters without gaps for a.c. systems', 2004
  4. ANSI standard C29.11, 'Composite Suspension Insulators for Overhead Transmission Lines Tests', 1996
  5. IEC Standard 61109, 'Composite insulators for a.c overhead lines with a nominal voltage greater than 1000 V -definition, test methods and acceptance criteria', 1992
  6. IEEE standard C62.11, 'Metal-oxide surge arresters for AC power Circuit', 1999
  7. A. Jeffrey and J. Kester, 'Multistress aging tests of polymer housed surge arresters', IEEE Trans. on Power Delivery, Vol. 13, No. 2, p. 446, 1998 https://doi.org/10.1109/61.660913
  8. R. Sundararajan, 'Multi stress accelerated aging of polymer housed surge arresters under simulated coastal florida conditions', Vol. 13, No. 1, p. 211, 2006 https://doi.org/10.1109/TDEI.2006.1593419
  9. 송일근, 한재홍, 김주용, '폴리머애자 경년열화 실증연구', 3차년도 중간보고서, 전력연구원, 2005
  10. T. G. Gustansson, 'Aging of silicone rubber under AC or DC voltages in a coastal environment', IEEE Trans on DEI, Vol. 8, p. 1029, 2001 https://doi.org/10.1109/94.971462
  11. R. Sundararajan, 'In-service aging and degradation of 345 kV EPDM transmission line insulators in a coastal environment', IEEE Trans. on DEI, Vol. 11, p. 348, 2004 https://doi.org/10.1109/TDEI.2004.1285906