Assessment of Rotor Winding Insulation Condition for Gas Turbine Generators

가스터빈 발전기 회전자 권선의 절연상태 평가

  • Published : 2008.10.01

Abstract

Several off-line diagnostic tests which include the insulation resistance(IR), polarization index(PI), low-voltage AC, and recurrent surge oscillograph(RSO) tests were performed to assess the condition of generator rotor windings. The low-voltage AC and the RSO tests were performed on the gas turbine generator rotor winding to detect shorted turns. Before intentionally applying artificial shorted faults, it was confirmed by the low voltage AC and the RSO tests that the winding was in sound condition. For simulated shorted rotor winding turns, the RSO test detected the fault in the winding. The RSO test was capable of identifying the number and pole location of the shorted turns for a number of simulated shorted coils.