A Dynamic Characteristics on Non-linear Voltage Electric Equipment under Voltage Sag

순간전압강하에 대한 비선형 저압전기기기의 동적특성

  • Published : 2008.03.01

Abstract

In this study, a transition of power quality was characterized by non-linear voltage electric equipments under voltage sag. The test was inputted voltage sag to IPC(Sag Generator) from AVR, and then to equipments by IPC which adjust voltage magnitude and duration. The load test which non-linear voltage electric equipments used PLC, Magnetic Contactor, SMPS, HID Lamp. The test result was different from each other according to a manufacturing companys, models, and equipments. PLC was greatly described to be stabilized voltage sag in case of no load then rated load. Magnetic Contactor was made a difference to phase angles on voltage sag, which was $0^{\circ}$, $30^{\circ}$, $60^{\circ}$, $90^{\circ}$. HPD Lamp was described to be stabilized the sodium lamp, and to be unstabilized the metal hailed lamp. The test result was showed CBEMA curve that stand for evaluated responsiveness of voltage sag. This study was tested description to dynamic characteristics on non-linear voltage electric equipment under voltage sag. There was hoped that power system designed the essential particulars.

Keywords

References

  1. 김지홍, 이상동, 김명찬, 이현원, 이준엽, "전력품질과 동적 순간전압강하 보상기의 적용", 전기저널, Dec.2000, pp32-39.
  2. 이은옹, 임수생, "전력품질에 대한 분석과 개선대책", 전기저널, Sep.2001, pp34-42.
  3. 원충연, "전원과 전력전자 시스템의 전력품질개선", 조명.전기설비학회지, 제14권, 제3호, 2000년 6월, pp68-74.
  4. IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Std. 1159-1995, Nov. 1995.
  5. IEEE Guide for Service to Equipment Sensitive to Momentary Voltage Disturbances, IEEE Std. 1250-1995, June 1995.
  6. IEEE Standard Terms for Reporting and Analyzing Outage Occurrences and Outage States of Electrical Transmission Facilities, IEEE Std. 859-1987, Feb.1988.
  7. Electromagnetic compatibility (EMC), ICE 61000-4-11.
  8. Specification for Semiconductor Processing Equipment Voltage Sag Immunity, SEMI F47-0200.
  9. Christopher J. Melhorn, Mark F. McGranghan, "Interpretation and Analysis of Power Quality Measurements", Textile, Fiber and Film Industry Technical Conference, 1995. IEEE 1995 Annual, May 1995, pp1-9.
  10. Geun-Joon Lee, Mihaela M. Albu, Gerald Thomas Heydt, "A Power Quality Index Based on Equipment Sensitivity, Cost, and Network Vulnerability", IEEE Trans. on Power Delivery, Vol. 19, No.3, July 2004, pp1504-1510. https://doi.org/10.1109/TPWRD.2004.829124
  11. Dong-Jun Won, Seon-Ju Ahn, Il-Yop Chung, Joong-Moon Kim, Seung-Il Moon, "A New Definition of Voltage Sag Duration considering The Voltage Tolerance Curve", IEEE Conf., 2003. Vol 3. pp5.
  12. 이근준, 이현철, 정성원, 김재현 "순간전압강하에 대한 저압기기의 응동특성 실험결과", 대한전기학회 전력기 술부문 추계학술대회, 2007, pp40-42.
  13. IEEE recommended practice for evaluating electric power system compatibility with elecronic process equipment, IEEE std. 1346, 1998.
  14. Bollen, M.H.J. Sabin, D.D. Thallam, R.S., "Voltagesag indices - recent developments in IEEE PI564 task force", Quality and Security of Electric Power Delivery Systems, 2003. CIGRE/PES 2003. CIGRE/IEEE PES International Symposium 8-10, Oct. 2003, pp34-41.
  15. J.Pedra, F. Corecoles, L. Sainz, "Study of AC contactors during voltage sags", Harmonics and Quality of Power, 10th International Conf., Vol. 2, 2002, pp565-570.