DOI QR코드

DOI QR Code

On the Fire Behavior Due to the Ventilation Condition in the Fire Compartment

환기 조건에 따른 화재거동 연구

  • 김성찬 (경일대학교 소방방재학부) ;
  • Published : 2008.05.01

Abstract

A series of fire experiments has been conducted to provide an improved understanding of the fire structure of under-ventilated compartment fires. A comprehensive and quantitative assessment of gaseous species from the fire was made in the upper layer of fire in a 40 % reduced scale ISO 9705 fire compartment. The global equivalence ratio (GER) concept was used to characterize the fire behavior for various fire sizes, fuel types and ventilation conditions. The oxygen concentration in the upper layer reached to zero near the global equivalence ratio of $0.4{\sim}0.6$ while the carbon monoxide concentration increases with increasing the global equivalence ratio. Classification parameters of ISO19706 were also compared with the reduced scale experimental data for under ventilation fire.

Keywords

References

  1. Hull, T. R., Quinn, R. E, Areri I. G. and Purser D. A. 2002., “Combustion Toxicity of Fire Retarded EVA,” Polymer Degradation and Stability, Vol. 77. No. 2, pp. 235-242 https://doi.org/10.1016/S0141-3910(02)00039-3
  2. Purser, D. A., 2002, “Toxicity Assessment of Combustion Products,” SFPE Handbook of Fire Protection Engineering, 3rd Edition
  3. Hull, T. R., Lebek, K., Pezzani, M. and Messa, S., 2007. “Comparison of Toxic Product Yields of Burning Cables in Bench and Large-scale Experiments,” Fire Safety Journal, In Press
  4. Hull, T. R. and Paul, K. T., 2007. “Bench-scale Assessment of Combustion Toxicity . A Critical Analysis of Current Protocols,” Fire Safety Journal, Vol. 42, No. 5. pp. 340-365 https://doi.org/10.1016/j.firesaf.2006.12.006
  5. ISO TS 19706, 2004, Guidelines for Assessing the Fire Threat to People
  6. Pitts, W. M., 1995, “The Global Equivalence Ratio Concept and Formation Mechanisms of Carbon Monoxide in Enclosure Fires,” Progress in Energy and Combustion Science, Vol. 21, No. 3, pp. 197-237 https://doi.org/10.1016/0360-1285(95)00004-2
  7. Kim, S. C., Hamins, A., Bundy, M., Johnsson, E. R., and Ko, G. H., 2007, “Analysis of Thermocouple Behavior in Compartment Fire,” Proceeding of 7th Aisa-Oceania Symposium on Fire Science and Technology, AOSFST, Vol. 1
  8. Bryant, R. A., Ohlemiller, T. J., Johnsson, E. L., Hamins, A., Grove, B. S., Guthrie W. F., Maranghides, A. and Mulholland, G., 2003, “NIST 3Megawatt Quantitative Heat Release Rate Facility,” NIST, SP 1007, Gaithersburg, MD
  9. Parker, W. J., 1984, “Calculations of the Heat Release Rate by Oxygen Consumption for Various Applications,” Journal of Fire Science, Vol. 2, No. 5, pp. 380-395 https://doi.org/10.1177/073490418400200505
  10. Bundy, Matthew, Maranghides, A., Johnsson, R., Kim, S. C. and DeLauter, L., 2007, “Heat Release Uncertainty in the NIST Large Fire Facility,” NIST Annual Fire Conference, Gaithersburg, MD
  11. Drysdale, D., 1998, “An Introduction to Fire Dynamics,” 2nd Edition, Wiley, UK
  12. Gottuk, D. T. and Lattimer, B. Y., “Effect of Combustion Conditions on Species Production,” SFPE Handbook of fire Protection Engineering, 3rd Edition
  13. Andersson, P., Rossel, L., Simonson, M, and Emanuelsson, V., 2004, “Small and Large Scale Fire Experiments with Electric Cables Under Wellventilated and Vitiated Conditions,” Fire Technology, Vol. 40, pp. 247-62 https://doi.org/10.1023/B:FIRE.0000026879.07753.86