시스템 에어컨 설치 공간의 실내공기질 특성에 관한 연구

A Study on Characteristics of Indoor- Air-Quality in Interior Space Equipped with System Air-Conditioner

  • Lee, Sang-Won (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Kim, Jong-Min (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Yeum, Seung-Won (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Cho, Dae-Gun (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Choi, Jae-Boong (School of Mechanical Engineering, Sungkyunkwan University) ;
  • Kim, Seok-Woo (Samsung Electronics Co. LTD.)
  • 발행 : 2008.05.10

초록

This paper investigates the indoor-air-quality (IAQ) characteristics of the interior space equipped with system air-conditioner. The behaviors of individual variables such as temperature, humidity and concentration of carbon dioxide ($CO_2$) that influence on IAQ of the interior space were characterized under various cooling conditions by numerical and experimental studies. The numerical analysis predicting the temperature behavior of the interior space was conducted, and its results showed a good agreement with the experimental ones. The $CO_2$ concentration and humidity were measured and their time dependent behaviors were monitored and analyzed. From the results, it was found that there existed the differences of the time-dependent behaviors of IAQ variables according to the locations. In addition, it is demonstrated that the large discharge angle of $45^{\circ}$ made the temperature profile more irregular and the high discharge flow of 5.34 m/s produced similar temperature profiles at three different sensing locations. Finally, the humidity of interior space was less sensitive to the changes of the air cooling conditions than the case of temperature and the $CO_2$ concentration increase mainly depended on the number of individuals inside the space.

키워드

참고문헌

  1. Lee, J. H., Kim, Y. J., Choi, W. S., Park, S. K., Youn, B. and Kim, Y. J., 2006, Evaluation of indoor thermal comfort for ceiling type system air-conditioner with various discharge angles, SAREK conference, pp. 1180-1185
  2. Kim, S. H., Noh, K. C. and Oh, M. D., 2003, Evaluation of thermal comfort in consideration of the solar radiation, Journal of SAREK, Vol. 16, No. 12, pp. 1140-1146
  3. Ahn, C. R., Kim, J. J., Kum, J. S. and Park, H. S., 2004, A study on the using the ventilation system as the method of improvement of air quality in the schools, Journal of Korean Institute of Education Facilities, Vol. 11, No. 2, pp. 17-23
  4. Noh, K. C., Jang, J. S. and Oh, M. D., 2006, Study on thermal comfort and indoor air quality in the classroom with system airconditioner and ventilation system for cooling loads, Transactions of the KSME B, Vol. 30, No. 1, pp. 57-66 https://doi.org/10.3795/KSME-B.2006.30.1.057
  5. Lee, K. H., Han, Y. H., 1995, A study on the thermal comfort draft requirements of low temperature floor heating system, Journal of Architectural Institute of Korea, Vol. 11, No. 12, pp. 171-177
  6. Lee, J. Y., 2005, The recent trend in personal comfort control, Journal of SAREK, Vol. 34, No. 4, pp. 42-48
  7. Kim, K. W., Lee, S. W., Lee, E. G. and Ryu, H. C., 2003, Architecture environment design, Taerim munhwa-sa
  8. Architecture Law, 2000, Regulations for equipment standard of architecture, Korea
  9. Patankar, S. V., 1980, Numerical heat transfer and fluid flow, McGraw-Hill Book Co.
  10. Jun. S. J. et al., 2005, Care of the adult patient, Hyunmun-sa
  11. ASHRAE Handbook, 1997, Space air diffusion, American Society of Heating, Refrigerating and Air-conditioning Engineers, Atlanta, Georgia