Instantaneous Active/Reactive Power Compensation of Distribution Static Compensator using State Observer

배전용 정지형 보상기의 상태관측기를 이용한 순시 유효/무효전력 보상

  • 김형수 ((주)포스콘 기술연구소) ;
  • 최종우 (경북대 전자전기컴퓨터학부)
  • Published : 2008.08.01

Abstract

DSTATCOM(distribution static compensator) is one of the custom power devices, and protects a distribution line from unbalanced and harmonic current caused by non-linear and unbalanced loads. Researches about DSTATCOM are mainly divided two parts, one is the calculation of compensation current and the other part is the current control. Conventional researches use a LPF(low pass filter) to eliminate ripple component at the calculation of compensation current. But this method has a problem that LPF's characteristics restrict the compensation performance of instantaneous active and reactive power. This paper proposes a calculation of compensation current using state observer that can be a counterproposal of conventional methods using LPF. Improved performance of instantaneous active and reactive power compensation was shown by experiments.

Keywords

References

  1. H. Akagi, Y. Kanazawa and A. Nabae, "Instantaneous reactive power compensators comprising switching devices without energy storage components", IEEE Transactions on Industry Applications, vol. 20, pp. 625-630, May/June 1984 https://doi.org/10.1109/TIA.1984.4504460
  2. F. Peng, J. Lai, "Generalized Instantaneous Reactive Power Theory for Three-Phase Power Systems", IEEE Transactions on Instrumentation and Measurement, vol. 45, no. 1, pp. 293-297, Feb. 1996 https://doi.org/10.1109/19.481350
  3. F. Peng, G. Ott, D. Adams, "Harmonic and Reactive Power Compensation Based on the Generalized Instantaneous Reactive Power Theory for 3-Phase 4-Wire Systems", IEEE Conference Records on PESC Annual Meeting '97, pp. 1089-1095, June 22-27, 1997
  4. S. Buso, L. Malesani, P. Mattavelli, "Comparison of Current Control Techniques for Active Filter Applications", IEEE Transactions on Industrial Electronics, vol. 45, no. 5, pp. 722-729, Oct, 1998 https://doi.org/10.1109/41.720328
  5. Sang-Joon Lee, Seung-Ki Sul, "A Harmonic Reference Frame Based Current Controller for Active Filter", Conf. Rec. IEEE-APEC Annu. Meeting, 2000, pp. 1073-1078
  6. R. Teodorescu, F. Blaabjerg, U. Borup, M. Liserre, "A new control structure for grid-connected LCL PV inverters with zero steady-state error and selective harmonic compensation", IEEE Conference Record APEC Annual Meeting '04, pp. 580-586, 2004
  7. 황희훈, 최종우, 김흥근, "전차원 상태 관측기를 이용한 단상 PLL제어의 특성 연구", 전력전자학회 추계학술대회 논문집, pp. 78-80, 2006. 11