An Algorithm of Predicting the Zone 3 Trip Time of Distance Relay by using PMU Data when Power Systems Face Cascaded Event on Transmission System

송전 계통의 광역정전 징후 시 PMU 취득 데이터를 이용한 거리계전기 Zone3 동작시간 예측 알고리증

  • Published : 2009.12.01

Abstract

Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be attributed to improper operations of protective relays. Especially, it is the most dangerous problem that trips of backup relays by overload. In this paper, a new algorithm of predicting Zone 3 acting time of distance relay is proposed using the real time synchronized data from PMUs on the transmission system when the power system is danger. In the proposed, some part of the power system are outage when some unexpected fault in the power system, the algorithm will monitor the impedance locus of distance relay. At this time, if there is a big change of Impedance locus, the algorithm will calculate the Zone 3 acting time of the distance relay by the over load. In the case studies, the estimation and simulation network have been testified and analysed in Matlab Simulink.

Keywords

References

  1. B.A. Carreras, V.E. Lynch, I. Dobson, D.E. Newman,' Critical points and transitions in an electric power transmission model for cascading failure blackout', Chaos, vol, 12, no. 4, December 2002, pp. 985-994 https://doi.org/10.1063/1.1505810
  2. P. Fairley. 'The Inruly Power Grid', IEEE Spectrum. pp. 22-27, August 2004.
  3. Gregory S. Vassell, Fellow, IEEE, 'Northeast Blackout of 1965', IEEE Power Review, pp. 4-8, January 1991 https://doi.org/10.1109/MPER.1991.88621
  4. 'NIGHT OF TERROR', TIME, pp. 24-26, July 25, 1977
  5. C. W. Taylor, 'Improving Grid Behavior. IEEE Spectrum. June 1999. pp. 40-45
  6. J, Chen, J. S. Thorp and M. Parashar. 'Analysis of Electric Power Proceedings of System the 34th Disturbance Data', Hawaii International Conference on System Science, 2001
  7. A.G. Phadke and J,S. Thorp, 'Expose Hidden Failure to Prevent Cascading Outages', IEEE Computer Application in Power, pp. 20-23, July 1996 https://doi.org/10.1109/67.526849
  8. Seong-Il Lim, Chen-Ching Liu, Seung-Jae Lee, Myeon-Song Choi and Seong-Jeong Rim. 'Blocking of Zone 3 Relays to Prevent Cascaded Events', Power Systes. IEEE Transactions on Volume 23, pp.747-754, May 2008 https://doi.org/10.1109/TPWRS.2008.919417
  9. Phadke, A.G and Thorp, J,S. 'Expose hidden failures to prevent cascading outages in power systems', Computer Applications in Power. IEEE, pp 20-23, July 1996 https://doi.org/10.1109/67.526849
  10. David C. Elizondo, J. de la Ree, Arun G. Phadke and Stan Horowitz, 'Hidden Failures in Protection System and their Impact on Wide-area Disturbances', IEEE, 2001. pp 710-714 https://doi.org/10.1109/PESW.2001.916941
  11. April 2000.U.S.-Canada Power System Outage Task Force, 'Final Report on the August 14, 2003 blackout m the United States and Canada'. http://wwwJerc.gov/, April, 2004
  12. Carson W. Taylor, Bonneville Administration, 'Improving Grid Behavior-The inglorious summer-of-1996 blackouts taught the west to improve emergency control and protection and to sharpen simulation techniques', IEEE SPECTRUM JUNE 1999, pp. 42-45