Enhanced Dynamic Response of SRF-PLL System in a 3 Phase Grid-Connected Inverter

3상 계통연계형 인버터를 위한 SRF-PLL 시스템의 동특성 개선

  • Published : 2009.04.20

Abstract

The new method is proposed to improve the dynamics of the phase angle detector during abrupt voltage dip caused by a grid fault. Usually, LPF(low pass filter) is used in the feedback loop of SRF(Synchronous Reference Frame) - PLL (Phase Locked Loop) system because the measured grid voltage contains harmonic distortions and sensor noises. A better transient response can be obtained with the proposed design method for SRF-PLL by the analysis of linearized model of the PLL system including LPF. Furthermore, in the proposed method, the controller gain and LPF cut-off frequency are changed from normal value to transient value when the voltage disturbance is detected. This paper shows the feasibility and the usefulness of the proposed methods through the computer simulation and the experiment.

전원사고로 인하여 야기되는 전원급변상황에서 위상각의 새로운 PLL 방법은 추종속도를 개선시키기 위하여 제안되었다. 일반적으로 측정된 전원이 이상적이지 않고 고조파가 포함되어 있으며 센서의 노이즈 때문에 동기좌표계 PLL의 피드백 루프에는 LPF를 사용하고 있다. 그러므로 과도상태의 빠른 동특성을 얻기 위해서 LPF를 고려한 PLL시스템의 모델링을 제안하였다. 또한 전원의 급변 시에 빠른 위상각 검출을 위한 방법으로 자동으로 제어기 대역폭과 LPF의 차단주파수를 변동시키는 가변 파라미터 PLL방법을 제안하였다. 이를 시뮬레이션과 실험을 통해 검증하여 유효성을 보이고자 한다.

Keywords

References

  1. Sang-Joon Lee, Jun-Koo Kang, Seung-Ki Sul, 'A new phase detecting method for power conversion systems considering distorted conditions in power system', Industry Applimtions Conference, Vol. 4, pp. 2167-2172, 1999
  2. Rodriguez, P., Pou, J., Bergas, J., Candela, I., Burgos, R., Boroyevic, D., 'Double Synchronous Reference Frame PLL for Power Converters Control', Proc. of PESC05, pp.1415 -1421, 2005
  3. Se Kyo Chung, 'A Phase Tracking System for Three Phase Utility Interface Inverters', IEEE Trans., Vol. 15, No.3, pp. 431-438, 2000
  4. M. Kamata, T. Shono, T. Saba, I. Sasase, S. Mori, 'Third-order phase-locked loops using dual loops with improved stability', IEEE Pacific Rim Conference, Vol. 1, pp. 20-22, Aug. 1997
  5. F. Blaabjerg and R. Teodorescu, M. Liserre, Adrian V. Timbus, 'Overview of Control and Grid Synchronization for Distributed Power Generation Systems', IEEE Trans. On Industrial Electronics, Vol. 53, No.5, 2006
  6. 김형수, 최종우, '전차원 상태관측기를 이용한 3상 불평형 전원의 PLL 성능 개선', 전력전자학술대회논문집, pp. 305-308, 2007. 7
  7. 최형진, 송승호, 정승기, 최주엽, 'LVRT를 위한 전원 전압 위상 및 크기의 고속 모니터링', 풍력에너지학술대회 논문집, 2008. 10
  8. 김윤현, 김왕래, 임창진, 김광섭, 권병기, 최창호, '불평형 계통전압에 강인한 연료전지용 전력변환시스템의 PLL 방법', 전력전자학술대회논문집, pp. 103-105, 2008. 6
  9. 김형수, 최종우, '정상분 전압 관측기를 이용한 불평형 3상 전원의 PLL', 전력전자학회 논문지, 제13권, 제2호, pp. 145-151, 2008. 4
  10. 김용균, 최종우, 김홍근, '디지털 PLL 제어의 특성 분석', 전력전자학술대회논문집, pp. 548-553, 2003. 7
  11. 김재형, 지용혁, 원충연, 정용채, '개선된 DFT를 이용한 위상 추종방법', 전력전자학술대회논문집, pp. 91-93, 2008. 6
  12. 목형수, 최규하, 이정민, 김상훈, 지준군, '계통연계형 인버터의 왜곡된 계통전압에 의해 발생하는 전류고조파 저감방법', 전력전자학술대회논문집, pp. 108-111, 2007. 11