DOI QR코드

DOI QR Code

The Design of a I/O Circuits for Driving and Monitoring of the Diesel Generator for Emergency

비상용 디젤 발전기 구동 및 모니터링을 위한 입출력 회로 설계

  • Published : 2009.08.31

Abstract

This paper presents an digital based input/output interface circuit for controlling and monitoring the Diesel Engine Generator for emergency. In order to monitor and control of the Emergency Diesel Engine Generator, controlling and monitoring circuits need 5 analog input channels, 2 pick-up coil measuring circuits, 10 digital input channels containing Broken Wire Detect function, and 7 relay control signal output channels. This system performs signal processing of input signal taking advantage of simple filter circuit, photo-coupler and comparator circuit at analog input parts, and output signals for main relay is designed acting by double control, so it prevents malfunction completely. And it improves accuracy of speed input signal by applying digital circuit that processes rick-up coil signal.

본 논문에서는 비상 디젤 엔진 발전기 제어 및 모니터링을 위해 제안된 디지털 기반의 입/출력 인터페이스 회로를 소매한다. 비상 발전기의 동작 상태를 모니터링 하고 제어하기 위해 제어 및 감시 회로는 5개의 아날로그 입력 채널과 2개의 픽업(Pick-up)코일 계측 회로, 브로컨 와이어(Broken Wire) 감지 기능을 가지는 10개의 디지털 입력 채널 및 7개의 릴레이 제어 신호 출력 채널이 요구된다. 본 연구에서는 아날로그 입력 단에 간단한 필터 회로와 포토커플러, 비교기 회로를 이용하여 입력 신호에 대한 신호처리를 수행하였으며, 중요한 릴레이 출력 신호들은 이중으로 단속될 수 있도록 설계하여 오동작을 철저히 방지하였다. 그리고 픽업코일 신호를 디지털 처리하는 회로를 적용하여 속도 신호 입력의 정확성을 향상 시켰다.

Keywords

References

  1. Ron Mancini(Editor in Chief), Op Amps for Everyone, Texas Instruments, 2003
  2. DNV, Environmental test specification for instrument- ation and automation equipment, April 2006