An Overcurrent Analysis in Neutral Line and Algorithm to Prevent Malfunction of Relay in Distributed Generations

분산전원 연계선로에서 지락고장시 중성선의 과전류 해석 및 보호계전기의 새로운 알고리즘

  • 신동열 (한전 전력연구원) ;
  • 김동명 (전력연구원 엔지니어링 센터) ;
  • 차한주 (충남대학교 전기정보통신공학부)
  • Published : 2009.10.01

Abstract

Introducing distributed generators(DGs) to utility distribution system can cause malfunction of relay on the grid when ground faults or severe load unbalances are occurred on the system. Because DGs interconnected to the grid can contribute fault currents and make bidirectional power flows on the system, fault currents from DGs can cause an interference of relay operation. A directional over current relay(DOCR) can determine the direction of power flow whether a fault occurs at the source side or load side through detecting the phases of voltage and current simultaneously. However, it is identified in this paper that the contributed fault current(Ifdg) from the ground source when was occurred to contribute single-line-to-ground(SLG) fault current, has various phases according to the distances from the ground source. It means that the directionality of Ifdg may not be determined by simply detecting the phases of voltage and current in some fault conditions. The magnitude of Ifdg can be estimated approximately as high as 3 times of a phase current and its maximum is up to 2,000 A depending on the capacity of generation facilities. In order to prevent malfunction of relay and damage of DG facilities from the contribution of ground fault currents, Ifdg should be limited within a proper range. Installation of neutral ground reactor (NGR) at a primary neutral of interconnection transformer was suggested in the paper. Capacity of the proposed NGR can be adjusted easily by controlling taps of the NGR. An algorithm for unidirectional relay was also proposed to prevent the malfunction of relay due to the fault current, Ifdg. By the algorithm, it is possible to determine the directionality of fault from measuring only the magnitude of fault current. It also implies that the directionality of fault can be detected by unidirectional relay without replacement of relay with the bidirectional relay.

Keywords

References

  1. 신동열, 박용우, 차한주 '분산형 발전고객의 OCGR오동작 및 과부족 계량에 대한 사례연구', 대한전기학회 논문지 57권 제8호, 2008년 8월
  2. R. F. Arritt, R. C. Dugan, 'Distributed generation interconnection transformer and grounding selection', Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE, pp. 1-7, 2008
  3. 조성수, 한상옥 '154KV 변전소 주변압기의 용량 및 운전조건이 22.9kV 배전계통에 미치는 영향', 대한전기학회 논문지 57권 제3호, 2008년 9월
  4. 신동열, 하복남, 정원욱, 차한주 '배전계통에서 변압기 결선에 의한 역조류현상에 관한 연구' 한국조명설비학회 논문지 22권 제9호, 2008년 9월
  5. 경기사업본부 관내 배전자동화 개폐기 '거짓 FI발생정보'에 대한 원인분석, 전력연구원 배전연구소 기술지원, 2008년 7월
  6. 분산형전원 배전계통 연계기술 해설서, 한국전력공사 배전처, 2006년 9윌
  7. Sukumar M. Brahma: Adly A. Girgis, 'Effect of Distributed Generation on Protective Device Coordination m Distribution System', Power Engineering, LESCOPE '01, Page(s):115-119, 2001