Abstract

This paper describes the development of a new islanding detection method for inverter-based distributed generation systems, which uses a signal cross-correlation scheme between the injected reactive current and the power frequency deviation. The proposed method injects 1% of the reactive current to the rated current which brings about a negligible degradation of the power quality. It discriminates the islanding state, when the calculated cross-correlation index is larger than 0.5. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software and experimental research with a hardware prototype. The proposed method can detect the islanding state without degrading the power quality at the point of common connection. Further study is required to overcome the cancellation of the injected reactive current from multiple distributed generation units interconnected with the utility grid.

Keywords

References

  1. M. E. Ropp, M.Begovic, and A.Robatgi, "Analysis and performance assessment of the active frequency drift method of islanding prevention," IEEE Trans. Energy Convers., Vol. 14, No. 3, pp.810-816, Sep. 1999. https://doi.org/10.1109/60.790956
  2. M. E. Ropp, M. Begovic, A. Rohatgi, "Determining the relative effectiveness of islanding prevention techniques using phase criteria and non-detection zones," IEEE Transactions on Energy Conversion, Vol. 15, No. 3 , pp. 290-296, Sep. 2000. https://doi.org/10.1109/60.875495
  3. W. Bower and M. Ropp, "Evaluation of islanding detection methods for photovoltaic utility-interactive power systems," International Energy Agency, Technical Report IEA PVPS T5-09, Mar. 2002.
  4. IEEE Std. 929-2000, IEEE Recommended Practice for Utility Interface of Photovoltaic(PV) Systems, Sponsored by IEEE Standards Coordinating Committee 32 on Photovoltaics, IEEE Std. 929-2000, Published by the IEEE, New York, NY, Apr. 2000.
  5. S. Juang and F. Pai, "A new approach to islanding detection of dispersed generators with self-commutated static power converters," IEEE Trans. Power Delivery, Vol. 15, No. 1, pp. 500-507, Apr. 2000. https://doi.org/10.1109/61.852975
  6. G.K. Hung, C.C Chang, and C.L. Chem, "Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters," IEEE Trans. Energy Conversion, Vol. 18, No. 1, pp. 169-173, Mar. 2003. https://doi.org/10.1109/TEC.2002.808412
  7. V. John, Z. Ye, and A. Kolwalkar, "Investigation of anti-islanding protection of power converter based distributed generators using frequency domain analysis," in Proc. IEEE Power Eng. Society General Meeting, Vol. 4, pp. 2452-2458, Jul. 2003.
  8. R. A. Walling and N. W. Miller, "Distributed generation islanding implications on power system dynamic performance," in Proc. IEEE Power Eng. Soc. Summer Meeting, Vol. 1, pp. 92-96, Jul. 2002.
  9. S. Jang and K. Kim, "An islanding detection method for distributed generations using voltage unbalance and total harmonic distortion of current," IEEE Trans. Power Delivery, Vol. 19, No. 1, pp. 745-752, Apr. 2004.
  10. F. Katiraei, M. R. Iravani, and P. W. Lehn, "Micro-grid autonomous operation during and subsequent to islanding process," IEEE Trans. Power Del., Vol. 20, No. 1, pp. 248-257, Jan. 2005. https://doi.org/10.1109/TPWRD.2004.835051
  11. G. Hernande-Gonzalez and R. Iravani, "Current Injection for Active Islanding Detection of Electronically-Interfaced Distributed Resources," IEEE Trans on Power Delivery, Vol. 21, No. 3, Jul. 2006.
  12. B. Han and B. Bae, "Novel Phase-Locked Loop Using Adaptive Linear Combiner," IEEE Trans on Power Delivery, Vol. 21, No. 1, Jan. 2006.

Cited by

  1. A review of islanding detection techniques for renewable distributed generation systems vol.28, 2013, https://doi.org/10.1016/j.rser.2013.08.025
  2. A sequence perturbation based islanding detection for distributed generation with periodic code matching vol.7, pp.1, 2015, https://doi.org/10.1063/1.4913266
  3. Comparative study of active anti-islanding schemes compatible with MICs in the prospect of high penetration levels and weak grid conditions pp.1751-8695, 2018, https://doi.org/10.1049/iet-gtd.2018.5636
  4. On the Injection of Sub/Inter-Harmonic Current Components for Active Anti-Islanding Purposes vol.11, pp.9, 2018, https://doi.org/10.3390/en11092183