DOI QR코드

DOI QR Code

The Audible Noise Prediction of the Substation due to Transformer Audible Noise and the Field Application of the Low Noise Transformer

변압기 소음에 의한 변전소 소음예측 및 저소음 변압기 현장적용

  • Received : 2010.05.18
  • Accepted : 2010.07.02
  • Published : 2010.08.01

Abstract

Recently, there has been a growing interest in the environmental conservation. Accordingly, problems related to the audible noise of transformers have became more frequent. Therefore, it is urgent to find a fundamental solution about the audible noises in the substations. This paper described a sort of fundamental solution to solve the noise problem. As a fundamental solution, we suggested the proper audible noise level of transformers through noise prediction in the substation construction phase. And we applied the low noise transformers which have the predicted noise level. As the result, we are able to satisfy the noise regulation through measuring 43.6dBA at the boundary of substation. It is confirmed that the average error rate of prediction was within 3 percent.

Keywords

References

  1. 권동진 외, "저소음 변압기 개발을 위한 기초 조사 연구," 한전전력연구원 최종보고서, pp.1-92, 2004.
  2. 권동진 외, "환경친화형 저소음 변압기 개발," 한전전력연구원 최종보고서, pp.1-121, 2008.
  3. ISO 9613 Part-2, "Attenuation of sound during propagation outdoors - General method of calculation," 1996.
  4. 구교선 외, "옥내 및 옥외 변전소의 소음예측을 통한 변압기 소음레벨 기준," 대한전기학회 전력용 변압기 워킹그룹 동계학술대회 논문집, pp.3-5, 2007.
  5. 구교선 외, "옥내변전소 운전상황에 따른 변압기 소음 예측," 한국조명전기설비학회 논문지, 제22권, 제10호, pp.104-110, 2008.
  6. 구교선 외, "변전소 소음예측 프로그램 개발," 대한전기학회 논문지, 제56권, 제9호, pp.1556-1560, 2007.
  7. 구교선 외, "옥내변전소 운전상황에 따른 변압기 소음 예측," 한국조명전기설비학회 논문지, 제22권, 제10호, pp.104-110, 2008.
  8. "변압기 소음레벨 기준치," 한국전력 표준규격 ES 5950-0009, 2006.