DOI QR코드

DOI QR Code

Review on the Relationship of Dissolved Gas Analysis and Internal Inspection of Transformer

변압기 절연재료 분석과 내부점검 결과와의 상관성 연구

  • 박현주 (한전 전력연구원 환경화학분석팀) ;
  • 남창현 (한전 전력연구원 환경화학분석팀) ;
  • 정년호 (한전 전력연구원 환경화학분석팀)
  • Received : 2010.08.19
  • Accepted : 2010.09.16
  • Published : 2010.10.01

Abstract

For reliable operation of oil-filled electrical equipment, monitoring and maintenance of insulating oil is essential. Dissolved gas analysis(DGA) is widely used for monitoring faults in high voltage electrical equipment in service. Therefore, oil analysis should be monitored regularly during its service life. KEPCO has investigated thousands of dissolved gas analysis data since 1985, and conducted studies on the relationship of gas in oil analysis and internal inspection results of transformer. As the results, KEPCO revised criteria for transformer diagnosis and has applied it since 2008. Almost of 100 cases of internal inspection results since 2001 have been investigated. This paper presents the correlation of the fault-identifying gases with faults found in actual transformers and how should we approach to internal inspection of transformer by dissolved gas analysis.

Keywords

References

  1. "Maintenance and Control of oil-immersed Electrical Equipment by Dissolved Gas Analysis", Society of Electrical Cooperative Research 36, No.1. 1980.
  2. IEC Pub.599, "Interpretation of the Analysis of gases in transformers and Other oil-Filled Equipment in Service", 1978.
  3. "유입전력용 변압기의 점검 및 관리기술과 운영시스템 개발", 한전 전력연구원, 최종보고서, 2008.
  4. C.E Lin, "An Expert System for transformer fault diagnosis using Dissolved Gas Analysis", IEEE Transactions on Power Delivery, Vol.8, No.1, January 1993.
  5. J.L.Guardado, "A Comparative Study of Neural network Efficiency in power Transformers Dignosis using Dissolved Gas Analysis", IEEE Transactions on Power Delivery, Vol.16, No.4, October 2001.
  6. IEEE std. C57.125-1991, IEEE Guide for Failure Investigation, Documentation, and Analysis for Power Transformers and Shunt Reactors
  7. Recent deveopments in DGA Interpretation, Joint task force D1.01, CIGRE, June 2006.
  8. Weidmann-ACTI Inc.Sixth Annual Technical Conference, St.Petersburg, FL Nov., 2007.
  9. Muhammad Arshard, "Power transformer Aging and life Extention", 8th International Conference on Probabilstic methods to Power Systems, Iowa state University, Ames, Iowa, September 12-16, 2004.
  10. "유입 변압기의 보수관리, 일본전기협동연구회", 제 54권, 제 5호, 1999.