DOI QR코드

DOI QR Code

Evaluation of Operation Practicality on Line with Aluminum Conductor in Underground T&D Systems

지중송전 및 배전계통에서 알루미늄 도체 선로운용의 실용성 평가

  • 장주영 (원광대 대학원 전기공학과) ;
  • 이종범 (원광대 공대 전기정보통신공학부) ;
  • 김용갑 (원광대 공대 전기정보통신공학부)
  • Received : 2010.11.29
  • Accepted : 2011.02.23
  • Published : 2011.03.01

Abstract

This paper describes that the evaluation on operation practicality of Al conductor cable will be used instead of Cu conductor cable. Analysis is divided into two kinds of cases as transmission and distribution. To evaluate that Al conductor line has the insulation strength indeed safely, various analysis and calculation such as single line-to-ground fault current, lightning surge and allowance current were carried. Model was established based on real combined transmission and distribution is being used in utility with EMTP. The analysis results on Al and Cu conductor line were compared each other. It was proved that Al conductor line can be operated instead of Cu conductor line without special insulation problem in transmission and distribution, in electrical view point such as overvoltage and allowance current.

Keywords

References

  1. KEPCO, "배전선 절연설계에 관한 연구[II]", 1992
  2. KEPRI, "지중송전 케이블의 써어지 보호 대책에 관한 연구(최종보고서)", 1993
  3. KEPCO, "배전계통 이상전압 측정 및 대책 연구", 2000
  4. 전력연구원, "지중송전계통의 접지기술 정립에 관한 연구(최종보고서)", 1998
  5. 우정욱, "송전선로 고장과 LPATS 낙뢰자료 DB와의 비교분석에 관한 연구", 대한전기학회 하계학술대회 논문집, 1999
  6. KEPCO, "배전계통 절연협조 기준 정립에 관한 연구(최종보고서)", 2003
  7. KEPCO, "설계기준-DS-1101", 2006
  8. KEPCO, "설계기준-DS-1210", 2003
  9. KEPCO, "설계기준 - 5300(지중구조물)", 2000
  10. KEPRI, "345kV 및 154kV Gapless형 피뢰기 정격 규격 및 기준 정립 연구(최종보고서)", 2000
  11. KEPRI, "지중송전계통 최적 시스템 구성 방안 정립에 관한 연구(최종보고서)", 2009
  12. KEPCO, "설계기준-3500(접지공사)", 1999
  13. KEPCO, "설계기준-5001(총칙)", 1998
  14. KEPCO, "설계기준-DS-5901", 2009