DOI QR코드

DOI QR Code

대형마트의 조명 및 냉방 에너지 분석 및 에너지 절감 연구

Analysis of Energy Consumption and Research on Energy Saving of Lighting and Coo1ing Energy of a Superstore

  • 투고 : 2010.08.06
  • 심사 : 2011.04.12
  • 발행 : 2011.05.10

초록

This study analyzes the current and after retrofit energy consumption of lighting and cooling system of a superstore in Seoul. Energy consumption data were measured and collected with a measurement system. Annual energy consumption was calculated using TRNSYS program. After replacing lighting and chiller with higher efficiencies, annual TOE consumption decreased from 1,066 before retrofit to 832 after retrofit, saving 234 TOE (22%) in total. Similarly, total annual $TCO_2$ consumption decreased from 2,214 to 1,721, reducing 493 $TCO_2$ (22%) during this pilot study.

키워드

참고문헌

  1. Korea Energy Management Corporation, 2004, Climate change protocol and our response, Ministry of Commerce, Industry and Energy.
  2. Um, C. J., Han, I. S., Kim, C. Y. and Kim, D. S., 2009, Tendency analysis and case xtudies through building audit, Proceedings of SAREK Winter Annual Meeting, pp. 164-169.
  3. Korea Energy Management Corporation, 2006, Operation code of energy audit.
  4. Japan Chain Store Age, 2008.
  5. Korea Trade Center Vienna, 2008.
  6. Solar Energy Laboratory, 2000, TRNSYS (Transient System Simulation) 15 Program, University of Wisconsin-Madison.
  7. Ministry of Knowledge and Economy, 2010, Regulations of energy law, Vol. 124.

피인용 문헌

  1. An Analysis of the Energy Saving Effect Through the Retrofit and the Optimal Operation for HVAC Systems vol.24, pp.4, 2012, https://doi.org/10.6110/KJACR.2012.24.4.343