DOI QR코드

DOI QR Code

A Study on Practicality of Condition Monitoring Method of Accelerated Thermal Aging CSPE

가속열화 된 CSPE 상태감시법 유효성 평가

  • 이정훈 (원광대학교 대학원 전기공학과) ;
  • 구철수 (한국원자력안전기술원 공학연구실) ;
  • 김인용 (한국원자력안전기술원 공학연구실) ;
  • 신용덕 (원광대학교 전기.정보통신공학부, 부설 공업기술개발연구소)
  • Received : 2011.09.20
  • Accepted : 2011.10.28
  • Published : 2011.11.01

Abstract

The accelerated thermal aging of CSPE(chloro sulfonate polyethylene) of test cables were carried out for the period equal to 10, 20 and 30 years in air at $100^{\circ}C$, respectively. The CSPE cables(TAIHAN electric wire Co. Ltd) which installed in nuclear power plant for three years were used as starting materials. Condition monitering methods of the accelerated thermal aging of CSPE cables were estimated through indenter modulus and OIT(oxidation induction time) of IEC 62582, and those were newly estimated through volume electrical resistivity, ultrasound reflection time, density, FE-SEM(field emission scanning electron microscopy), XPS(x-ray photoelectron spectroscopy), EDS(energy dispersive spectroscopy), and WD-XRF(wavelength dispersive x-ray fluorescence). A new condition monitoring methods of the accelerated thermal aging of CSPE cables were generally coincident with trend of indenter modulus expect EDS, XPS and XRF. A volume electrical resistivity among new condition monitoring methods of the accelerated thermal aging of CSPE cables is excellent. It is considered that life-time of CSPE cable can be predicted through volume electrical resistivity, if CSPE jacket was aged for period such as more than 20 years.

Keywords

References

  1. 한국전력거래소, "2010년 전력시장분석보고서"
  2. Draft Regulatory Guide DG-1240, "Condition monitoring program for electric cables used in nuclear power plants", Division 1, June, 2010.
  3. US NRC NUREG/CR-7000, "Essential Elements of an electric Cable Condition Monitoring Program", Brookhanven National lavoratory Upton, NY, January, 2010.
  4. T. Andrews, R.N. Hampton, A. Smedberg and D. Wald, "The Role of Degassing in XLPE power cable manufacture", IEEE Electrical Insulation, Vol. 22, No. 6, 2006.