DOI QR코드

DOI QR Code

A Study on the Performance Evaluation of a Hybrid Desiccant Cooling System

하이브리드 제습냉방시스템의 성능평가 연구

  • 황원백 (고려대학교 기계공학과 대학원) ;
  • 김용찬 (고려대학교 기계공학과) ;
  • 이대영 (한국과학기술연구원 에너지메카닉스 연구센터)
  • Received : 2010.12.30
  • Published : 2012.02.10

Abstract

Improvement in the energy efficiency has been studied of the desiccant cooling system by applying a vapor compression type heat pump to modify the system into a hybrid system. The cycle simulation was performed and the results were compared between a reference desiccant cooling system composed of a desiccant rotor, a sensible rotor and a regenerative evaporative cooler, and a hybrid desiccant cooling system with the sensible rotor being replaced by a heat pump. Though the electric consumption increases as much as the compressor power consumption, the total cooling capacity increases and the thermal energy input decreases by the addition of the heat pump. Therefore, the total energy efficiency can be improved if the increase in the electric consumption can be compensated with the increase in the cooling capacity and the decrease in the thermal energy input. The results showed that the total energy efficiency is optimized at a certain heat pump capacity. When the heat from the CHP plant is used for the thermal energy input, the energy consumption of the hybrid system is reduced by 20~30% compared with the reference system when the heat pump shares 30~40% of the total cooling capacity.

Keywords

References

  1. Dhar, P. L. and Singh, S. K., 2001, Studies on solid desiccant based hybrid air-conditioning systems, Applied thermal Engineering, Vol. 21, pp. 119-134. https://doi.org/10.1016/S1359-4311(00)00035-1
  2. Jia, C. X., Dai, Y. J., Wu, J. Y., and Wang, R. Z., 2006, Analysis on a hybrid desiccant airconditioning system, Applied thermal Engineering, Vol. 26, pp. 2393-2400. https://doi.org/10.1016/j.applthermaleng.2006.02.016
  3. Jain, S., Dhar, P. L., and Kaushik, S. C., 1995, Evaluation of solid-desiccant-based evaporative cooling cycles for typical hot and humid climates, Int. J. Refrigeration, Vol. 18, pp. 287- 296. https://doi.org/10.1016/0140-7007(95)00016-5
  4. Lee, J. W., Lee, D.-Y., and Kang, B. H., 2004, Cycle simulation of a desiccant cooling system with a regenerative evaporative cooler, Korean J. Air-Conditioning and Refrigeration Engineering, Vol. 16, pp. 566-573.
  5. Goldsworthy, M. and White, S., 2011, Optimisation of a desiccant cooling system design with indirect evaporative cooler, Int. J. Refrigeration, Vol. 34, pp. 148-158. https://doi.org/10.1016/j.ijrefrig.2010.07.005
  6. Choi, B. S., Hong, H., and Lee, D.-Y., 2008, Study on the counterflow regenerative evaporative cooler with finned channels, Korean J. Air-Conditioning and Refrigeration Engineering, Vol. 20, pp. 447-454.
  7. Zheng, W. and Worek, W. M., 1993, Numerical simulation of combined heat and mass transfer process in a rotary dehumidifier, Numerical Heat Transfer, Part A, Vol. 23, pp. 211- 232. https://doi.org/10.1080/10407789308913669
  8. Lee, G., Lee, D.-Y., and Kim, M. S., 2004, Development of a linearized model and verificaverification of the exact solution for the analysis of a desiccant dehumidifier, Korean J. Air-Conditioning and Refrigeration Engineering, Vol. 16, pp. 811-819.
  9. Fischer, S. K. and Rice, C. K., 1983, The Oak Ridge Heat Pump Models:I. A Steady-state Computer Design Model for Air-to-Air Heat Pumps, ORNL, CON-80, R1.
  10. Xia, L. Chan, M. Y., Deng, S. M., and Xu., X. G., 2009, A modified logarithmic mean enthalpy difference(LMED) method for evaluating the total heat transfer rate of a wet cooling coil under both unit and non-unit Lewis Factors, Int. J. Thermal Sciences, Vol, 48, pp. 2159- 2164. https://doi.org/10.1016/j.ijthermalsci.2009.04.002
  11. Rice, C. K., 1991, The ORNL modulating heat pump design tool user's guide.
  12. White, S. D., Goldsworthy, M., Reece, R., Spillmann, T., Gorur, A., and Lee, D.-Y., 2011, Characterization of desiccant wheels with alternative materials at low regeneration temperatures, Int. J. Refrigeration, In Press, Available online.
  13. Moon, H.-K. and Lee, D.-Y., 2008, Cooling performance of a counterflow regenerative evaporative cooler with finned channels, Korean J. Air-Conditioning and Refrigeration Engineering, Vol. 20, pp. 462-469.
  14. Euroheat and Power, 2007, Guidelines for assessing the efficiency of district heating and district cooling systems, Report of Ecoheatcool Work Package 3, http://www.euroheat.org/eco heatcool.

Cited by

  1. Performance Analysis of Hybrid Desiccant Chiller Based on Field Test vol.37, pp.7, 2013, https://doi.org/10.3795/KSME-B.2013.37.7.621
  2. Thermoeconomic Analysis of Hybrid Desiccant Cooling System Driven by District Heating vol.38, pp.9, 2014, https://doi.org/10.3795/KSME-B.2014.38.9.721