DOI QR코드

DOI QR Code

Analysis of Withstand Voltage between Arc Contacts of High Voltage SF6 Gas Circuit Breaker n Making Operation

초고압 SF6 가스 차단기 투입 시 아크접촉자 내전압 특성 연구

  • Received : 2012.02.15
  • Accepted : 2012.02.29
  • Published : 2012.04.01

Abstract

The non-controlled closing of High-voltage SF6 gas circuit breaker can cause transient current and overvoltage in the field. The controlled closing technology is an effective way to reduce transient current and voltage, prevent equipment failures, and improve power quality. For the development of controlled closing, it is obviously necessary to determine the withstand voltage between arc contacts of High-voltage SF6 gas circuit breaker in making operation. This paper focuses on decrease of pressure and density of SF6 gas that can affect withstand voltage between arc contacts in making operation. The dielectric strength between arc contacts could be improved by minimizing the decrement of pressure and density of SF6 gas obtained by simulation and test and moreover the rate of decrease of dielectric strength (RDDS) of arc contacts could be foreseen.

Keywords

References

  1. CIGRE TF13.00, "Controlled Switching, A State-of-the-Art Survey Part 1", ELECTRA, No.162, pp.65-96, 1995.
  2. CIGRE TF13.00, "Controlled Switching, A State-of-the-Art Survey Part 2", ELECTRA, No.164, pp.39-61, 1996.
  3. CIGRE WG 13.07, "Controlled Switching of HVAC Circuit-Breakers, Guide for Application Part 1", ELECTRA, No 183, pp 43-73, April 1999.
  4. CIGRE WG 13.07, "Controlled Switching of HVAC Circuit-Breakers, Guide for Application Part 2", ELECTRA, No.185, pp.37-57, August 1999.
  5. 김홍규외 4인, "SF6 가스차단기의 소전류 차단성능 해석", 대한전기학회 논문지, Vol. 55B, No. 10, pp. 528-533, 2006.
  6. H. Hamada외 7인, "RDDS(rate of decrease of dielectric strength) measurement for gas circuit breaker", IEEE/PES Transmission and Distribution Conference and Exhibition 2002, Vol. 3, pp. 1755-1759, Oct 2002.
  7. H. Kohyama외 6인, "Development of 550kV and 362kV synchronous switching gas circuit breaker", IEEE/PES Transmission and Distribution Conference and Exposition 2001, Vol. 1, pp. 597-602, 2001.
  8. 김익수, "초고압 전력기기의 최적설계를 위한 가스중절연특성 연구", 한국전기연구원, pp. 64-66, 1995.