DOI QR코드

DOI QR Code

Transferred OverVoltages on LV sides in Multigrounded Neutral during Line to Ground Fault on Distribution Systems

배전계통의 고저압 혼촉고장시 중성선 전위상승에 따른 저압기기 스트레스 전압

  • 최선규 (한국전력공사 전력연구원) ;
  • 최종기 (한국전력공사 전력연구원) ;
  • 김경훈 (한국전력공사 인재개발원) ;
  • 최명호 (한국전력공사 서울지역본부 성동지사) ;
  • 이병성 (한국전력공사 전력연구원)
  • Received : 2011.09.09
  • Accepted : 2011.12.12
  • Published : 2012.06.01

Abstract

In this paper we propose multi-grounded neutral design method which was considered of transferred transient overvoltage when line to neutral fault occurs. Specially, In order to confirm the actual transient overvoltage magnitude which occurs on neutral line, we considered some screening(shielding) effects. The screening coefficient was deducted from field test results and calculation in a distribution line which is identical with an actual power line. The purpose of this paper is to attempt to suggest the guidance for grounding skystem design considering limitation of overvoltage for LV side in IEC 61936. The result is based on EMTP simulation and real field faults situation in distribution lines.

Keywords

References

  1. Korea Electric Association, "A Survey Report of Electro-Technical Regulation", KEPCO's Technical Report, 2007.
  2. H.S. Kim, J.H. Chung, K.M. Kang, "Effects of Ground Faults on the Safety of Persons and Low-voltage Installations in 22.9 kv-Y Distribution Systems", Journal of KIIEE, Vol. 22, No.1, pp.141-148, Jan. 2008. https://doi.org/10.5207/JIEIE.2008.22.1.141
  3. Y. Rajotte, J. Fortin, and C. Raymond, "Impedance of multigrounded neutrals on rural distribution systems", IEEE Trans. Power Del., Vol. 10, no. 3, pp.1453-1459, Jul. 1995. https://doi.org/10.1109/61.400929
  4. International Electrotechnical Commission, "IEC 61936-1, Power installations exceeding 1 kV a.c.", IEC std., pp.86, 2010.
  5. A.L. Clapp, "NESC Handbook", IEEE Press, Sixth edition, pp.66-74, 2006.
  6. S.K. Choi, J.K. Choi, G.Y. Jung, K.H. Kim, K.B. Sim, "An Examination of Hazardous Voltage for Human Safety in KEPCO distribution line", Proceeding of the 41th the KIEE Summer Annual Conference, pp.2122-2123, Jul. 2010.
  7. J.R Acharya, Y. Wang, and W. Xu, "Temporary Overvoltage and GPR characteristics of Distribution Feeder with Multigrounded Neutral", IEEE Trans. on Power Del., Vol. 25, no. 2, pp.1036-1044, Apr. 2009.
  8. Y. Rajotte, J. Fortin, B. Cyr, and G. Raymond, "Characterization of the ground impedance of rural MV lines on Hydro-Quebec's system", IEE, Proc. CIRED, Conf. Publ. no. 438, pp.17/1-17/5, Jun. 1997.
  9. K. Oka, J. Yoshinaga, S. Koizumi, S. Uemura, and Y. Ariga, "Study of neutral grounding for 22 kV distribution systems", IEEE PES, T&D Conf. and Expo. : Asia Pacific, Vol. 3, pp.2143-2148, Oct. 2002.
  10. K. Oka, S. Koizumi, K. Oishi, T. Yokota, and S. Uemura, "Analysis of neutral grounding method for a three-phase four-wire 11.4 kV distribution system", IEEE PES, T&D Conference and Exposition: Asia Pacific, Vol. 2, pp.998-1003, Oct. 2002.
  11. T.H. Chen and W.C. Yang, "Analysis of multi-grounded four-wire distribution systems considering the neutral grounding", IEEE Trans. Power Del., Vol. 16, no. 4, pp.710-717, Oct. 2001. https://doi.org/10.1109/61.956760
  12. L. Agudelo, R.H. Ortiz, M. Montoya, C. Cardenas, K.C. Echeverri, and G. Moreno, "Transferred voltages in multigrounded systems", IEEE PES, T&D Conference and Exposition: Latin America, Aug. 2008.