DOI QR코드

DOI QR Code

The vibration detection and analysis of 3-phase cast resin transformer in less than 50% load conditions

50% 미만 부하조건에서의 3상 몰드변압기 진동 측정과 분석

  • 송길목 (한국전기안전공사 전기안전연구원) ;
  • 방선배 (한국전기안전공사 전기안전연구원) ;
  • 김종민 (한국전기안전공사 전기안전연구원) ;
  • 김영석 (한국전기안전공사 전기안전연구원) ;
  • 최명일 (한국전기안전공사 전기안전연구원)
  • Received : 2012.02.23
  • Accepted : 2012.06.22
  • Published : 2012.07.01

Abstract

In this paper, we were analyzed the vibration characteristics of the three-phase cast resin transformer using less than 50% of load in the field. Most of the cast resin transformer is less than 50% in the domestic field is used for load conditions. Consisting of a solid insulator cast resin transformer is generating lots of noise and vibration. In addition, because it is affected by Joule 's heat is used in light load conditions. As a results, the transformer vibrations at frequencies below about from 200Hz to 500Hz were detected. Vibration velocity depends on the load variations were found. Load up to approximately 20-30% in most cases the vibration velocity was found at 4,000 ${\mu}m/s$ or less, 8,000 ${\mu}m/s$ or more. Vibration frequency at light load conditions were generated at the 120Hz, 240Hz, 360Hz and 480Hz. At the load condition of from 10% to 20%, vibration velocity is higher than another. Most of the vibration velocity were identified at the 1,000 ${\mu}m/s$ or less. Using the vibration frequency and velocity measurements data, the load on the cast resin transformer analyzed the correlation of the burden. Therefore, this data could be found in the vibration characteristics of the light-load conditions. If the field measurements using the data perform diagnostics on the transformer, it's expected to be very effective.

Keywords

References

  1. R. Vogelsang et al., "The Effect of Barriers on Electrical Tree Propagation in Composite Insulation Materials", IEEE Trans. on DEI Vol. 13, No. 1, pp.373-382, Apr. 2006 https://doi.org/10.1109/TDEI.2006.1624282
  2. Peter H.F. Morshuis, "Degradation of Solid Dielectrics due to Internal Partial Discharge: Some Thoughts on Progress Made and Where to Go Now", IEEE Trans. on DEI Vol. 12, No. 5, pp.905-913, Oct. 2005 https://doi.org/10.1109/TDEI.2005.1522185
  3. Yong-Han Yoon, Chi-Hyoung You, Jae-Chul Kim, Chan-Soo Chung and Jung-Jin Lee, "Fault Discrimination of Power Transformers using Vibration Signal Analysis", Trans. KIEE, Vol. 48A, No. 1, pp.1-7, 1999
  4. 한국전기안전공사, "전기재해통계분석", 제20호, 2011. 12.
  5. Young Park, Ho-Sung Jung, Chulmin Park and Soon-ho Jang, "Implementation of a Condition Monitoring System for Mold Transformers in DC Substations", Trans. KIEE, Vol. 60, No. 9, pp.1788-1794, 2011 https://doi.org/10.5370/KIEE.2011.60.9.1788
  6. 송길목, 최명일, 김영석, 방선배, 김종민, "부하 형태에 따른 몰드변압기에서의 진동 데이터 비교에 관한 연구", Journal of th KIIEE(2012), Vol. 26, No. 4, pp.75-81, 2012
  7. 김종민, 송길목, 방선배, 김영석, 최명일, "몰드변압기 진동특성과 파손가능성 검증", 2011 KIEE 전기설비부문회 춘계학술 논문집, 2011
  8. 송길목, 방선배, 김종민, 김영석, 최명일, 이명준, "몰드 변압기 진단을 위한 레이저 진동검출 시스템 개발", 2011 KIEE 전기설비부문회 춘계학술 논문집, 2011

Cited by

  1. A Study on the Comparison of Denoising Performance of Stationary Wavelet Transform for Discharge Signal Data in Cast-resin Transformer vol.28, pp.3, 2014, https://doi.org/10.5207/JIEIE.2014.28.3.084