A Study on Characteristic of $CO_2$ and TVOC Sensor based Ventilation Control Strategies according to the Evaluation of Indoor Contaminant Level in an Apartment House

공동주택 실내오염농도 평가에 의한 $CO_2$와 TVOC 센서기반 환기제어방법 특성 연구

  • 홍성민 (경원대학교 일반대학원 건축설비공학과) ;
  • 윤동원 (경원대학교 건축설비공학과)
  • Received : 2011.10.25
  • Published : 2012.01.25

Abstract

The purpose of this study is to find the control strategies for ventilation and energy reduction with appropriate maintenance of indoor contaminant levels. According to a survey in other research, many mechanical ventilation systems are not often operated by residents, because residents tend to avoid powering their ventilation system in order to save utility cost. There isn't anything to inform sufficiently how to operating ventilation system for IAQ(Indoor Air Quality). And then, without any sufficient ventilation control strategies, it would be very difficult to improve IAQ by an occupant's manual control. If the ventilation unit is operating for 24 hour, the energy consumption would be dramatically increased. Therefore, the sensor based DCV control method is necessary for comfort and energy saving. It has been simulated both of $CO_2$ and TVOC sensors based DCV system for operating mechanical ventilation system. As a result of analysis, $CO_2$-DCV is not sufficient to maintain for comfort IAQ against TVOC from building materials and furnitures. Because $CO_2$ is generated irregularly by occupant's schedules in individual room, but TVOC is emitted steadily from the finishing materials Therefore, $CO_2$-DCV couldn't control the chemical contaminants like TVOC as below as the guideline. We must consider whether chemical contaminants are a proper target for control in an apartment house or not, because TVOC are more dangerous than $CO_2$.

Keywords

Acknowledgement

Supported by : 국토해양부

References

  1. 김형준, 박준석, 환기설비 운전이 공동주택 연가 에너지소비량에 미치는 영향에 관한 연구, 대한건축학회 발표논문집 29(1), 2009
  2. 김광수, 실별 환기설비, 한국설비기술협회지, v.27, n.06, pp.71-80, 2010
  3. 홍성민, 윤동원, 김성수, 전동식댐퍼가 장착된 공동주택용 다 분기챔버에 의한 실별 환기풍량제어 성능평가, 한국생활환경학회지17(5), 2010
  4. 홍성민, 윤동원, 공동주택 멀티존 CO2센서기반 환기제어특성 연구, 대한건축학회논문집 계획계, 27(9), 2011
  5. 김진효, 권오현, 조 현, 김관우, 김현배, 정재원, 수요기반환기량 조절법의 공동주택 적용방안, 대한건축학회 발표논문집 29(1), 2009
  6. http://www.senseair.com, "What is CO2_DCV_rev1"
  7. ASHRAE, Ventilation for Acceptable Indoor Air Quality, Standard 62.1-2007
  8. 윤동원, 김효준, 김지헌, 성남철, 김성수 USN 기반의 실내환경 측정 및 관리를 위한 VOCs 센서의 동작특성 평가 연구, 한국건축친환경설비학회 논문집 3권 2호, 2009
  9. 통계청, 인구주택총조사, 2005
  10. 환경부, 생활용품에서 방출되는 오염물질 현황 및 관리방안 연구, 2006