DOI QR코드

DOI QR Code

A Experimental Study on the Heat Release Rate to activate Fire Detection Sensor

화재감지 센서 작동시간 및 열방출률에 대한 실험연구

  • Received : 2012.07.02
  • Accepted : 2012.07.25
  • Published : 2012.09.01

Abstract

This paper presents a study on the analysis for activation time and threshold value of heat detection sensor using HRR(Heat Release Rate). And it is represented to quantity of heat to activate heat detection sensor. The experiment is conducted to measure activation time and HRR of fire detection sensor burning alcohol and n-heptane. In order to burn the alcohol and n-heptane using $43.5cm(L){\times}43.5cm(W){\times}5cm(D)$ and $33cm(L){\times}33cm(L){\times}5cm(D)$ steel pan and the quantity of alcohol and n-heptane are 2.5 L and 650 g, respectively. The results show that peak HRR are in case of alcohol 66.13 kW and in case of n-heptane 151.64 kW, respectively. Total heat releases of heat detection sensor are in case of alcohol approximately 20.7 MJ and in case of n-heptane approximately 18 MJ, respectively.

Keywords

References

  1. Richard W. Bukowski and Robert J. OLughlin, Fire Alarm Signaling Systems Handbook, NFPA, pp.2-4, 1993
  2. Shu Yan, Shu Wang and Zheng Dou, "An Energy Model in Fire Detection and Integrated Ananysis on False Alarms", 12th International Conference on Automatic Fire Detection, 2001
  3. 백동현, 소방전기시설론, pp.115-123, 동일출판사, 2005
  4. 소방방재청 고시 제 2011-1호, 감지기 형식승인 및 검정에 관한 기준, 2011
  5. 편집부, 센서의 원리와 사용법, 도서출판 세화, p.45-53, 1991
  6. 김상진, 자동화를 위한 센서, 형학사, pp.54, 1991
  7. ISO 7240-9, Fire Detection and Fire Alarm Systems