DOI QR코드

DOI QR Code

Performance Analysis of an Air-Cycle Refrigeration System

공기사이클 냉동시스템의 성능해석

  • Won, Sung-Pil (School of Mechanical Engineering, University of Ulsan)
  • 원성필 (울산대학교 기계공학부)
  • Received : 2012.06.29
  • Published : 2012.09.10

Abstract

The objective of this study is to analyze theoretically the performance of an open air-cycle refrigeration system in which environmental concerns increase. The pressure ratio of the external compressor and efficiencies of the components that compose of the system are selected as important parameters. As the pressure ratio of the external compressor increases, the pressure ratio of the ACM compressor is determined high, the refrigerating temperature and capacity increase, the COP decreases, and the total entropy production rate increases. The effect of heat exchanger effectiveness and turbine efficiency on the performance are greater than that of the ACM compressor efficiency. Also the performance of the air-cycle refrigeration system with two heat exchangers has been enhanced like high COP and low total entropy production rate, compared to the system with one heat exchanger.

Keywords

References

  1. Kim, Y. M., 2005, Air cycle refrigeration technology, Journal of the KSME, Vol. 45, No. 8, pp. 23-25.
  2. Bhatti, M. S., 1998, Open air cycle air conditioning system for motor vehicles, SAE Paper No. 980289.
  3. Spence, S. W. T., Doran, W. J., and Artt, D. W., 2004, Design, construction and testing of an air-cycle refrigeration system for road transport, Int. J. of Refrigeration, Vol. 27, pp. 503-510. https://doi.org/10.1016/j.ijrefrig.2004.02.003
  4. Spence, S. W. T., Doran, W. J., Artt, D. W., and McCullough, G., 2005, Performance analysis of a feasible air-cycle refrigeration system for road transport, Int. J. of Refrigeration, Vol. 28, pp. 381-388. https://doi.org/10.1016/j.ijrefrig.2004.08.005
  5. Wang, X. and Yuan, X., 2007, Reuse of condensed water to improve the performance of an air-cycle refrigeration system for transport applications, Applied Energy, Vol. 84, pp. 874-881. https://doi.org/10.1016/j.apenergy.2007.01.018
  6. Kim, J. J. and Kim, T. S., 2006, Design parameter analysis of a reverse Brayton cycle refrigerator using natural working fluids, Proceedings of the SAREK winter conference, pp. 410-415.
  7. Kim, J. J. and Kim, T. S., 2007, Proceedings of the SAREK summer conference, pp. 127-132.
  8. Figliola, R. S. and Tipton, R., 2000, An exergybased methodology for decision-based design of integrated aircraft thermal systems, SAE Paper No. 2000-01-5527.
  9. Conceicao, S. T. and Turcio, W. H. L., 2007, Thermodynamic study of aircraft air conditioning air cycle machines : 3-wheel x 4-wheel, SAE Paper No. 2007-01-2579.
  10. Zhao, H., Zhu Y., and Chen S., 2009, Experimental study on the performance of an aircraft environmental control system, Applied Thermal Engineering, Vol. 29, No. 16, pp. 3284-3288. https://doi.org/10.1016/j.applthermaleng.2009.05.002