Performance Evaluation of the Capillary Tube Radiant Floor Cooling & Heating System

모세유관 바닥복사 냉·난방 시스템의 성능평가

  • Received : 2012.06.14
  • Accepted : 2012.08.14
  • Published : 2012.08.31

Abstract

At present, many countries are trying to reduce green gas emissions to mitigate the effects of these gases on climate change. Year after year, there have been efforts to cut energy use for heating and cooling. Heating and cooling systems, common in all forms of housing, are increasing due to the constant supply of new housing resulting from improvements in economic growth and the quality of life. Thus, studies related to the design of cooling and heating systems to improve energy efficiency are expanding. Among the new designs, radiant floor cooling and heating systems which use capillary tubes are becoming viable means of reducing energy use. Radiant floor cooling and heating systems which use capillary tubes are creative and sustainable systems in which cool and hot water is circulated into capillary tube which has small diameter. In this study, the cooling and heating performance of this type of capillary tube system is investigated in an experimental study and a simulation using TRNSYS. The results of the experimental study show that under a peak load, a capillary tube radiant floor cooling system using geothermal energy can achieve desired indoor temperature without an additional heat source. The set room air temperature is maintained while the floor surface temperature, PMV and PPD remain within the comfort range. Also, this system is more economic than a packaged air conditioner system due to its higher COP. The results of the simulation show that the capillary tube radiant floor heating system maintains set temperature more stable than a PB pipe radiant floor heating system due to its lower supply temperature of hot water. In terms of energy consumption, the capillary tube radiant floor heating system is more efficient than the PB pipe radiant floor heating system.

Keywords

References

  1. Wilson, A., Radiant floor heating warms up, Architecture Journal, July 124-126, 1989
  2. 조동우, 강재식, 공동주택 바닥난방시스템의 성능개선 연구, 한국건설기술연구원 연구보고서,1995
  3. 이주연, The Effect of Water Cooled Floor on Thermal Comfort of the Human Body, 한국생환환경학회지 제7권 제2호, p.21, 2000
  4. 조영흠, 공동주택 현장실험을 통한 바닥복사냉방의 성능평가, 2004
  5. B. W. Olesen, International standares of the indoor environment, 2004
  6. S.B. Leigh, A Study for Evaluating Performance of Radiant Floor Cooling Integrated with Controlled Ventilation, 2005
  7. 이영주, 폴리프로필렌 모세유관 냉방시스템의 적용에 관한 실험적 연구, 2005
  8. 원종서, 초에너지 절약주택에서 바닥복사냉방시스템의 적용성 평가, 2008
  9. 홍희기, 김시환, 온돌 난방에 대한 동적 시뮬레이션, 대한설비공학회, 2009
  10. 김진옥, 저에너지 친환경 공동주택에서 모세유관 바닥복사냉방 시스템의 성능평가, 2010