DOI QR코드

DOI QR Code

바닥 복사난방 배관설비에서 배관파열 사례 연구

A Case Study on the Plumbing Pipe Burst of Floor Radiant Heating

  • 정홍도 (한국폴리텍IV대학 아산캠퍼스) ;
  • 신용한 (경상대학교 대학원 정밀기계공학과) ;
  • 박진관 (부산외국어대학교) ;
  • 정효민 (경상대학교 에너지기계공학과.해양산업연구소) ;
  • 정한식 (경상대학교 에너지기계공학과.해양산업연구소)
  • Jung, Hong-Do (Asan Campus of Korea PolytechnicIV) ;
  • Shin, Youn-Han (Department of Mechanical and Precision Engineering, Gyeongsang National University) ;
  • Park, Chen-Kwan (Pusan University of Foreign Studies) ;
  • Jeong, Hyo-Min (Department of Energy and Mechanical Engineering, The Institute of Marine Industry, GyeongSang national University) ;
  • Chung, Han-Shik (Department of Energy and Mechanical Engineering, The Institute of Marine Industry, GyeongSang national University)
  • 투고 : 2012.03.20
  • 발행 : 2012.10.10

초록

Heating pipes burst was occurred in the apartment complex that was applied floor radiant heating system. There were two opinions for the cause of the bursted heating pipes that was the flaw during construction and defects in the product and also there were conflicting among them. Officials analyzed it in order to investigate the cause of the rupture. Tensile test results showed different tensile strength between the lower part of heating pipe and the upper part of heating pipes. The lower tensile strength is maintained while the top was not secured. The reason why rupture heating pipes is that flow velocity isn't secured and then the air get stagnant. Stagnant air makes hardening. It is caused rupturing. The proper flow rate was confirmed 0.166 m/sec after experiment. It isn't make stagnant air inside heating pipes.

키워드

참고문헌

  1. Ministry of Construction and Transportation, Korea National Housing Corporation, Hyundai Engineering and Construction Co., Ltd, Kumkang Engineering and Construction Co., Ltd Joint authorship, 1996, '1st Study report of Development and Application of Floor Heating System in Apartment Housings in 1996.'
  2. The Rules Article 4 about 'Facilities Standards of Construction', revised in 11. 05. 1999.
  3. Kim, J. H., 2005, The Report of analysis 'Heating- piping bursted cause' in Anyang M-Apartment.
  4. Published Korean Standards Association by Rule book, 2010, 'KS M 3357.'
  5. Lee, S. Y. et al., 2009, AE Characteristic under Tensile of Polyethylene for Low Pressure Pipe, A Journal of The Korean Society for Power System Engineering, Vol. 7, No. 1.
  6. Kim, J. H., Dongbang Engineering Co., Ltd, 2005, The investigation Report of Tensile strength in Korea testing and research institute.
  7. Hong, S. J. et al., 2005, A Study on the Strategy to Maintain Optimal Flow-rate and Pressure of the Piping System for Individual Heating, Proceeding of the SAREK 2005 Summer Conf., pp. 9-13.
  8. Park, C. K. et al., 2010, Necessity off Optimal Current in Floor Heating System, Proceeding of the SAREK 2010 Summer Conf., pp. 151- 157.
  9. Hong, H. K. and Kim, S. H., 2005, Method of Dynamic Simulation for Ondol Heating, Proceeding of the SAREK 2009 Winter Conf., pp. 145-150.
  10. A Mannual of The Society of Air-conditioning and refrigerating engineers of Korea, in 2011, The 2nd book Air conditioning in 3rd Edition, The Heating System in 2nd Edition, The Hot-water heating in Chapter 2, pp. 2-9.