Development of Prevention Apparatus for Short-Circuit Faults Using the Line Voltage Drop of Neutral Wire

중성선 선로 전압강하를 이용한 단락사고 방지용 보호장치 개발

  • Kwak, Dong-Kurl (Graduate School of Disaster Prevention, Kangwon Univ.) ;
  • Kim, Jin-Hwan (Graduate School of Disaster Prevention, Kangwon Univ.) ;
  • Lee, Bong-Seob (Dept. of Control Instrumentation Eng., Kangwon University)
  • Received : 2012.10.18
  • Accepted : 2012.11.14
  • Published : 2012.12.01

Abstract

The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with such electric faults, specially short circuit faults. Earth Leakage Circuit Breaker (ELB) and Molded_case Circuit Breaker (MCCB), that is, Residual Current Protective Devices (RCDs) used on low voltage distribution lines cut off earth leakage and overload, but the RCD can not cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied in low voltage distribution panel are prescribed to rated breaking time about 30ms(KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To improve such problem, this paper proposes a prevention apparatus using the line voltage drop of neutral wire and some semiconductor switching devices. Some experimental tests of the proposed apparatus confirm the validity of the analytical results.

Keywords

References

  1. NEMA, "National Fire Statistics Analyses", 2011.
  2. KESCO, "Electric Disaster Statistics Analyses", 2011.
  3. R. N. Anderson, "What Came First? The Arc Bead or the Fire?", EC&M 100, pp. 20-21, 2001.
  4. V. Babrauskas, "Fire due to Electric Arcing : Can 'Cause' Beads Be Distinguished from 'Victim' Beads by Physical or Chemical Testing?", Fire and Materials 2003, Interscience Communications Ltd., pp. 189-201, 2003.
  5. C. S. Choi, D. W. Kim, Y. S. Kim, and K. Y. Lee, "The Arc Dispersion Properties by Switching of High Sensitivity Type RCD Contacts", Journal of KIFSE, Vol. 19, No. 2, pp. 63-68, 2005.
  6. S. I. Lee, J. G. Yoo, J. C. Park, and G. H. Choe, "Design and Development of Distorted Source Device for Circuit Breakers Failure Analysis", Trans. of KIPE, Vol. 11, No. 5, pp. 480-488, 2006.
  7. LSIS co., and Cheil Electric co., "Technical Data of ELB and MCCB", 2010.
  8. D. K. Kwak, "Development of RCD Auxiliary Trip Device by using High Precision Current Sensor", Trans. of KIEE, Vol. 58, No. 8, pp. 1532-1537, 2009.
  9. S. H. Choi, D. K. Kwak, and J. H. Kim, "A Study on Device Development for Electrical Fire Protection on Open Phase of Three-Phase Motor"", Journal of KIFSE, Vol. 26, No. 1, pp. 61-67, 2012.

Cited by

  1. Development of Arc Fault Interruption Control Circuit of Fault Voltage Sensing Type vol.27, pp.2, 2013, https://doi.org/10.7731/KIFSE.2013.27.2.001
  2. Development of Arc Fault Circuit Interrupter Using the Distorted Voltage Wave in Electric Arc Faults vol.62, pp.6, 2013, https://doi.org/10.5370/KIEE.2013.62.6.876