DOI QR코드

DOI QR Code

웨이브렛 계수를 이용한 고저항 지락고장 감시데이터 산출방법 연구

A Study on the Developing Method of HIF Monitoring Data using Wavelet Coefficient

  • 정영범 (전력연구원 파워시스템연구소) ;
  • 정연하 (전력연구원 파워시스템연구소) ;
  • 김길신 (전력연구원 파워시스템연구소) ;
  • 이병성 (전력연구원 파워시스템연구소) ;
  • 배승철 (국립과학수사연구원)
  • Jung, Young-Beom (Dept. of Power System, KEPCO Research Institute) ;
  • Jung, Yeon-Ha (Dept. of Power System, KEPCO Research Institute) ;
  • Kim, Kil-Sin (Dept. of Power System, KEPCO Research Institute) ;
  • Lee, Byung-Sung (Dept. of Power System, KEPCO Research Institute) ;
  • Bae, Seung-Chul (Dept. of Forensic Science, National Institute of Science Investigation)
  • 투고 : 2012.11.08
  • 심사 : 2013.01.28
  • 발행 : 2013.02.01

초록

As the increasing HIF(High Impedance Fault) with the arc cannot be easily detected for the low fault current magnitude compared to actual load in distribution line. However, the arcing current shows that the magnitude varies with time and the signal is asymmetric. In addition, discontinuous changes occur at starting point of arc. Considering these characteristics, wavelet transformation of actual current data shows difference between before and after the fault. Althogh raw data(detail coefficient) of wavelet transform may not be directly applied to HIF detection logic in a device, there are several developing methods of HIF monitoring data using the original wavelet coefficients. In this paper, a simple and effective developing methods of HIF monitoring data were analized by using the signal data through an actual HIF experiment to apply them to economic devices. The methods using the sumation of the wavelet coefficient squares in one cycle of the fundamental frequency as the energies of the wavelet coefficeits and the sumation of the absolute values were compared. Besides, the improved method which less occupies H/W resouces and can be applied to field detection devices was proposed. and also Verification of this HIF detection method through field test on distribution system in KEPCO power testing center was performed.

키워드

참고문헌

  1. John Tengdin, Ron Westfall, Kevin Stephan, High Impedance Fault Detection Technology, IEEE PES PSRC Working Group D15
  2. KEPCO(Korea Electric Power Corporation), 1987, A Study for the Improvement of the Protection Relay Scheme on Multi-grounded Distribution System, KEPCO RI Final Report, p41
  3. B. Don Russell, Ram P. Shinshali, C. J. Kim, Behavior of Low Frequency Spectra during Arcing Fault and Switching Events, IEEE Transaction on Power Delivery Vol. 3, Oct. 1998, p1487
  4. Seung-Hun Lee, Dong-Hwan Yoon, Introduction to the Wavelet Transform, Jinhanbook, 2003, p31
  5. High Impedance Fault Detection, F. B. Costa(Brazil) ISH, hannover, Germany, Aug. 2011
  6. Hyun Kim, Chul-Hwan Kim, High Impedance Fault Detection using Wavelet transform, KIEE, Vol. 48A, Dec. 1999, p1496
  7. http://wavelets.pybytes.com/wavelet/db4
  8. Carl L. Benner, B. Don Russell, Practical High-Impedance Fault Detection on Distribution Feeders, IEEE Transaction on Industry Applications Vol. 33, May/June 1997
  9. Ground Alert, Reliable detection of High-Impedance Fault caused by Downed Conductor, ABB Review, Jan. 2004