Abstract

This study is to compare energy consumption of air-source, ground-source and dual-source heat pump systems during intermediate season using dynamic simulation. Ground-source heat pump has higher COP than that of air-source but requires additional power consumption of auxiliary equipment such as circulation pump. During intermediate season when the outdoor air temperature is favorable, total COP of air-source heat pump may be greater than that of ground-source when circulation pump power consumption is included. Dual-source heat pump which selects the more favorable heat source is compared with air-source only and ground-source only heat pumps for total power consumption. Results show that power consumption of dual-source heat pump is lower than that of ground-source only by 0.73%.

Keywords

References

  1. Cho, H. G., 2012, Recent Trends of Development of Utilized technology of Heat Pump, Machinery Industry, Vol. 42, No. 1, pp. 95-99.
  2. Lee, J. Y., 2012, Heat Pump Technology for Saving Building Energy, KETEP Issue Paper, Vol. 1, pp. 3.
  3. TRNSYS(Transient System Simulation program) 17.
  4. Indoor temperature and humidity standards for calculation of air-conditioner capacity, 2013, Building Energy Conservation Design Standards, Korea, Attached Table 8.
  5. Lee, E. G., 1990, A Development of Thermal Analysis Program for Sellecting Wall Components in Energy conscious Design, Ministry of Science and Technology, Korea, pp. 33-37.
  6. Chung, K. S., Kim, K. W., Ahn. B. W., 2005, Building Air Conditioning System, Sungandang, Seoul, pp. 59.
  7. Public Facilities with Mechanical Ventilation System and Ventilation Rate, 2013, Regulation for Facility in Building, Korea, Attached Table 1-6.
  8. ASHRAE 62.1-2004.
  9. GLD(Ground Loop Design).
  10. Check List of Using Ground-Source studies, 2011, Korea Energy Management Corporation, Korea, pp. 3.