DOI QR코드

DOI QR Code

An Accuracy Improvement on Acquisition Time of SCADA RTU Status Event

SCADA RTU 상태이벤트 취득시간 정확도 개선

  • Lee, Ju-Heon (Information Security Team, KEPCO) ;
  • Lee, Sang-Joong (Dept. of Electrical Engineering, Seoul National University of Science and Technology)
  • 이주헌 (한국전력 정보보안팀) ;
  • 이상중 (서울과학기술대학교 전기공학과)
  • Received : 2012.09.03
  • Accepted : 2012.12.21
  • Published : 2013.03.01

Abstract

SCADA RTU is a remote control unit equipped in substations for automatic operation of a power system. The RTU monitors and measures the operation status of remote substations to transmits the signals to upper SCADA system and receives control command signals from dispatch center to actuate corresponding apparatus. The RTU receives the standard time from GPS receiver to synchronize the times for all devices and acquires the status event of power apparatus using DIM. Without the time synchronization between GPS and RTU, stable operation of the power system and accurate analysis of the system fault are impossible due to the time error of SOE. In this paper, a test is performed to identify if the operation time of SCADA RTU DIM coincides with the standard time. And we tried to find the reason of error, to minimize the time discrepancy. Through this study, RTU operation time could be synchronized with the standard time within 10[ms] to improve the reliability of SOE data.

Keywords

References

  1. Kyung-Hoon Chung et al, Textbook Basic course of ICT for recruits "Understanding of power automation system", KEPCO Academy, August 2012
  2. Ju-Heon Lee et al, Textbook Advanced course of Substation SCADA system "DNP communications understanding and data analysis", KEPCO Academy, October 2011
  3. IEEE-SA Standard Board, "IEEE Standard for Electric Power systems Communication - Distributed Network Protocol(DNP3)", IEEE Power & Energy Society, 2010
  4. Dong-Joo Kang and Rosslin John Robles, "Compartmentalization of Protocols in SCADA Communication", International Journal Of Advanced Science and Technology Volume 8, July, 2009
  5. Jin-Hee Kim et al, Textbook Fourth-generation SCADA system technology "IEC61970 Overview", KEPCO Academy, March 2012
  6. Ju-Heon Lee, Bong-hee Lee, Sang-Dong Jeon and Do-Won Kim, "A Study of GIS Fault Area Detection Algorithm by SCADA System", The Korean Institute of Electrical Engineers Summer Conference Papers, July 2010
  7. Ju-Heon Lee and Sang-Joong Lee, "On the Time Synchronization of SCADA RTU Digital Input Module", The Korean Institute of Electrical Engineers Summer Conference Papers, July 2012
  8. Ju-Heon Lee et al, Textbook Advanced course of Substation SCADA system "SCADA Remote Terminal Unit", KEPCO Academy, October 2011
  9. DaeYun Kwon, IlGwon Jung, DongSu Kim, HyunMo Lee, Gwang-Gyun Jung and DongHoon Jeon, "A Study on a Measurement of Synchro-phasor in Jeju-Island Power System using PMU(Phasor Measurement Unit)", The Korean Institute of Electrical Engineers Summer Conference Papers, July 2010
  10. Gi-Bum Lee and Young-Sik Kim, "A Study on PMU using the time code bit stream of a satellite", Korean Institute of Intelligent Systems, April 2011
  11. Sung-Eun Lee et al, Textbook Training course of EMS Remote Terminal Unit, "DNP communications understanding and data analysis", KEPCO Academy, November 2011
  12. Sung-Ho Jang et al, User Manual of SCADA M-RTU "RTU time synchronization procedures", GENAD Systems, 2012
  13. Jun-Hyung Park et al, User Manual of SCADA M-RTU "Main Processing Device Operating technology", YOUHO Electric, 2012
  14. SP-6 Contributing Members; John Ferraro et al, "Synchronized Event Data Reporting", New York, 2005
  15. Myung-Hee Lee et al, Textbook Power System Protection & Operating Communication technology "Power System Protection Communication technology", KEPCO Academy, August 2011
  16. Jung-hoon Lee, Hong-hee Lee, Gwan-su Kim, "A Study on Implementation of IRIG-B Protocol for Clock Synchronization for IEC 61850 Process Level", Journal of power electronics, July 2007
  17. Gwan-su Kim, Dinh Nhat Nguyen and Hong-hee Lee, "A Study on Clock Synchronization at IEC61850 Process Level", Journal of power electronics, June 2006

Cited by

  1. Development of Smart Remote Terminal Unit for Water Treatment SCADA System vol.28, pp.2, 2014, https://doi.org/10.5207/JIEIE.2014.28.2.024