DOI QR코드

DOI QR Code

A Compensation of the Grid Current Unbalance and Distortion caused by the Grid Voltage Unbalance and Distortion in 3-Phase Bi-Directional DC to AC Inverter

3상 양방향 인버터의 계통전압 불평형 및 왜곡에 의한 계통전류 불평형 및 왜곡 보상

  • Received : 2012.09.27
  • Accepted : 2013.01.02
  • Published : 2013.04.20

Abstract

This paper presents an algorithm of a compensation of the grid current distortion caused by the grid voltage unbalance and distortion in 3-phase bi-directional DC to AC inverter. Usually 3-phase grid system has unbalance and distortion because of connecting 1-phase and non-linear load with 3-phase load using same input node. Controlling 3-phase inverter by general method under the unbalanced and distorted grid voltage, the grid current has distortion. This distortion of the grid current cause the grid voltage distortion again. So, it need to control the grid current balanced and non-distorted, even the grid voltage gets unbalanced and distorted. There are some complex method to compensate the gird current distortion. it suggest simple method to solve the problem. Simulation and experiment is used to validate the proposed algorithm.

Keywords

References

  1. M. T. Tsai, and W. I. Tsai, "Analysis and Design of Three Phase AC to DC Converters With High Power Factor and Near-Optimum Feedforward," IEEE Transactions on Industrlal Electronics, Vol. 46, No. 3, June 1999.
  2. V. Blasko and V. Kaura, "A new mathematical model and control of a three-phase AC-DC voltage source converter," IEEE Transactions on Power Electronics, Vol. 12, issue 1, pp. 116-123, Jan. 1997. https://doi.org/10.1109/63.554176
  3. P. Enjeti and S. A. Choudhury, "A new control strategy to improve the performance of a PWM AC to DC converter under unbalanced operating conditions," in Proc. IEEE Pesc Conf., pp. 382-389, 1991.
  4. H. S. Song and K. Nam, "Dual current controller PWM converter under unbalanced input voltage conditions," IEEE Trans. on Ind. Elec., Vol. 46, No. 5, pp. 953-959, 1999. https://doi.org/10.1109/41.793344
  5. J. I. Jang, D. C. Lee, D. and H. G. Kim, "Current Control of Three-Phase PWM Converters under Unbalanced and Distorted Source Voltage," The Trans. of the KIPE, Vol. 12, No. 1, pp. 27-36, 2007.
  6. M. Liserre, R. Teodorescu, and F. Blaabjerg, "Multiple harmonics control for three-phase grid converter systems with the use of PI-RES current controller in a rotating frame," IEEE Trans. on Power Elec., Vol. 21, No. 3, pp. 836-841, 2006. https://doi.org/10.1109/TPEL.2006.875566
  7. S. D. Yang, J. Y. Choi, "The Study of 3-Phase Bi-Directional DC to AC Inverter for the Bi-Modal PV PCS," KSES Annual Spring Conference, Vol. 32, No. 1, pp. 319-324, 2012.
  8. J. W. Kim, D. H. Kang, J. H. Chang, J. M. Kim, "A Study on Sensorless Control of Transverse Flux Rotating Motor Based on MRAS with Parameter Estimation," Journal of Power Electronics, Vol. 11, No. 6, pp. 864-869, 2011. https://doi.org/10.6113/JPE.2011.11.6.864
  9. Sang-Joon Lee, Jun-Koo Kang, and Seung-Ki Sul, "A New Phase Detecting Method for Power Conversion Systems Considering Distorted Conditions in Power System," Industry Applications Conference, 1999. Thirty-Fourth IAS Annual Meeting. Conference Record of the 1999 IEEE.

Cited by

  1. Compensation of Unbalanced PCC Voltage in an Off-shore Wind Farm of PMSG Type Turbines vol.20, pp.1, 2015, https://doi.org/10.6113/TKPE.2015.20.1.1