DOI QR코드

DOI QR Code

Multi-Impedance Change Localization of the On-Voltage Power Cable Using Wavelet Transform Based Time-Frequency Domain Reflectometry

웨이블릿 변환 기반 시간-주파수 영역 반사파 계측법을 이용한 활선 상태 전력 케이블의 중복 임피던스 변화 지점 추정

  • Lee, Sin Ho (Dept. of Electrical and Electronic Engineering, Yonsei University) ;
  • Choi, Yoon Ho (Dept. of Electronic Engineering, Kyonggi University) ;
  • Park, Jin Bae (Dept. of Electrical and Electronic Engineering, Yonsei University)
  • 이신호 (연세대학교 전기전자공학과) ;
  • 최윤호 (경기대학교 전자공학과) ;
  • 박진배 (연세대학교 전기전자공학과)
  • Received : 2012.11.09
  • Accepted : 2013.04.12
  • Published : 2013.05.01

Abstract

In this paper, we propose a multi-impedance changes localization method of on-voltage underground power cable using the wavelet transform based time-frequency domain reflectometry (WTFDR). To localize the impedance change in on-voltage power cable, the TFDR is the most suitable among reflectometries because the inductive coupler is used to inject the reference signal to the live cable. At this time, the actual on-voltage power cable has multi-impedance changes such as the automatic section switches and the auto load transfer switches. However, when the multi-impedance changes are generated in the close range, the conventional TFDR has the cross term interference problem because of the nonlinear characteristics of the Wigner-Ville distribution. To solve the problem, the wavelet transform (WT) is used because it has the linearity. That is, using WTFDR, the cross term interference is not generated in multi-impedance changes due to the linearity of the WT. To confirm the effectiveness and accuracy of the proposed method, the actual experiments are carried out for the on-voltage underground power cable.

Keywords

References

  1. R. Papazyan and R. Eriksson "Calibration for time domain propagation constant measurements on power cables," IEEE Trans. on Instrumentation and Measurement, vol. 52, no. 2, pp. 415-418, Apr., 2003. https://doi.org/10.1109/TIM.2003.811657
  2. H. V. Hamme, "High-resolution frequency-domain reflectometry by estimation of modulated superimposed complex sinusoids," IEEE Trans. on Instrumentation and Measurement, vol. 41, no. 6, pp. 762-767, Dec., 1992. https://doi.org/10.1109/19.199407
  3. Y. J. Shin, E. J. Powers, T. S. Choe, C. Y. Hong, E. S. Song, J. G. Yook and J. B. Park, "Application of time-frequency domain reflectometry for detection and localization of a fault on a coaxial cable," IEEE Trans. on Instrumentation and Measurement, vol. 54, no. 6, pp. 2493-2500, Dec., 2005. https://doi.org/10.1109/TIM.2005.858115
  4. K. S. Kwak, S. H. Doo, C. K. Lee, J. B. Park and T. S. Yoon, "Reduction of the blind spot in the time-frequency domain reflectometry," IEICE Electronics Express, vol. 5, no. 8, pp. 265-270, Apr., 2008. https://doi.org/10.1587/elex.5.265
  5. S. H. Doo, W. S. Ra, T. S. Yoon and J. B. Park, "Fast time-frequency domain reflectometry based on the AR coefficient estimation of a chirp signal," Proc. of American Conrol Conf., pp. 3423-3428, Jun., 2010.
  6. S. H. Lee, J. B. Park and Y. H. Choi, "Wavelettransform- based time-frequency domain reflectometry for reduction of blind spot," Measurement Science and Techonology, vol. 23, no. 6, 065004, May, 2012. https://doi.org/10.1088/0957-0233/23/6/065004
  7. S. H. Lee, C. K. Lee, J. B. Park and K. S. Kwak, "Impedance change localization for live underground cable using time-frequency domain reflectometry," IEICE Electronics Express, vol. 9, no. 5, pp. 359-364, Mar., 2012. https://doi.org/10.1587/elex.9.359
  8. J. Wang, P. E. Stone, Y. J. Shin and R. A. Dougal, "Application of joint time-frequency domain reflectometry for electric power cable diagnostics," IET Signal Processing, vol. 4, no. 4, pp. 395-405, Aug., 2010. https://doi.org/10.1049/iet-spr.2009.0137
  9. J. Wang, P. Crapse, Y. J. Shin and R. A. Dougal, "Diagnostics and prognostics of electric cables in nuclear power plants via joint time-frequency domain reflectometry," Proc. of IEEE International Symposium Electrical Insulation, pp. 24-27, Jun., 2008.
  10. J. Wang, P. Crapse, Y. J. Shin and R. A. Dougal, "Diagnostics and prognostics of electric cables in ship power systems via joint timefrequency domain reflectometry," Proc. of IEEE International Conf. on Instrumentation and Measurement Technology, pp. 917-921, May, 2008.
  11. J. C. Goshwami and A. K. Chan, Fundamentals of wavelets: theory, algorithms, and application, New York: Wiley, 1999.
  12. P. Shukla, "Complex wavelet transforms and their applications," M.S. thesis, Dept. Electronic and Electrical Eng., Univ. Strathclyde, Glasgow, U.K., 2003.
  13. J. Driesen and R. Belmans, "Time-frequency analysis in power measurement using complex wavelets," Proc. of IEEE Int. Symp. on Ciruits and Systems, pp. 681-684, Aug., 2002.
  14. L. G. Weiss, "Wavelets and wideband correlation processing," IEEE Signal Processing Magazine, vol. 11, no. 1, pp. 13-32, Jan., 1994. https://doi.org/10.1109/79.252866
  15. O. Chaari, M. Meunier and F. Brouaye, "Wavelets: a new tool for the resonant grounded power distribution systems relaying," IEEE Trans. on Power Delivery, vol. 11, no. 3, pp. 1301-1308, Jul., 1996. https://doi.org/10.1109/61.517484