Abstract

The fault current of the power transmission system is greater than that of the power distribution system. Therefore, the introduction of superconducting fault current limiter (SFCL) is more needed to reduce the increased fault current. The trigger-type SFCL consists of the high-temperature superconducting element (HTSC), the current limiting reactor (CLR) and the circuit breaker (CB). The trigger-type SFCL can be used to supplement the disadvantages of the resistive-type SFCL. The operation characteristics of the current ratio differential relay which is usually applied to the protection device of the power transmission system are expected to be affected under fault conditions and the applicability of the trigger-type SFCL. In this paper, we analyzed the operating characteristics, by the fault conditions, between the current ratio differential relay for line protection and the trigger-type SFCL in the power transmission system through the PSCAD/EMTDC simulation.

Keywords

References

  1. 3th phase program of DAPAS (Development of Advanced Power system by Applied Superconductivity technologies), KERI, 2011.
  2. Lee, S. R, Kim, J. Y, Choi, H. K, Yoon, J. Y, "Feasibility Study on the Application of 154㎸ HTS-FCL in Korean Power System", Journal of KIEE, Vol. 53A, No. 12, pp. 661-669, 2004.
  3. Lee, S. R, Yoon, J. Y, Yang, B. M, "Protection system of new superconducting power system", KIEE, Vol. 2011, No. 7, pp. 292-293, 2011.
  4. Lee, S. R, Yoon, J. Y, Hwang, I. T, Yang, B. M, "A basic study on the activating current of 154KV SFCL", KIEE, Vol. 2012, No. 4, pp. 40-42, 2012.
  5. Lee, S. R, Yoon, J. Y, Hwang, I. T, Yang, B. M, "A basic study on the current limiting resistance/reactance for the application of 154KV SFCL to Korean power systems", KIEE, Vol. 2012, No. 4, pp. 37-39, 2012.
  6. Hyun, O. B, Park, K. B, Sim, J, Kim, H. R, "Introduction of a Hybrid SFCL in KEPCO Grid and Local Points at Issue", Journal of KIEE, Vol. 19, No. 3, pp. 1946-1949, 2009.
  7. Choi, J. S, Kim, M. H, You, I. K, Kim, J. S, Lim, S. H, Kim, J. C, "Analysis on Current Limiting and Recovery Characteristics of a Trigger Type SFCL as the Composition of the Contact", Journal of KIIEE, Vol. 24, No. 9, pp. 159-164, 2010. https://doi.org/10.5207/JIEIE.2010.24.9.159
  8. Cho, Y. S, Kim, J. S, Kim, M. H, Kim, Y. K, Noh, S. E, Lim, S. H, Kim, J. C, "Anaysis on Operating Characteristics between the Current Ratio Differential Relay and the Overcurrent Relay in s Loop Power Distribution System with the introduction of Trigger-type SFCL", KIEE, pp. 129-130, 2012.
  9. H. Y. Li, E. P. Southen, and P. A. Crossley, "A New Type of Dirrerental Feeder Protection Relay Using the Global Positioning System for Data Synchronization", IEEE, Vol. 12, No. 3, pp. 1090-1099, 1997.
  10. Lee, J. B, "Graphical Modeling for Operational Scheme of Current Differential Relay for Transmission Line Protection", KIEE, Vol. 1999, No. 7, pp. 1407-1409, 1999.
  11. Choi, M. S, Lee, S. J, Kang, S. H, Bae, Y. J, Cho, B. S, Yoo, Y. S, "A Study on the Protective Relay Setting Rules for 765KV Power System by Analysis of Errors", Journal of KIEE, Vol. 52A, No. 1, pp. 50-57, 2003.
  12. Kang, Y. C, Yun, J. S, Kim, D. Y, "A Current Differential Relaying Algorithm for Bus Protection Using a Compensating Algorithm of Secondary Currents of CTs ", Journal of KIEE, Vol. 49A, No. 9, pp. 446-450, 2000.