Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

  • Received : 2013.01.24
  • Accepted : 2013.07.04
  • Published : 2013.08.25

Abstract

Partial discharge diagnosis techniques using ultra high frequencies do not affect load movement, because there is no interruption of power. Consequently, these techniques are popular among the prevention diagnosis methods. For the first time, this measurement technique has been applied to the GIS, and has been tested by applying an extra high voltage switchboard. This particular technique makes it easy to measure in the live state, and is not affected by the noise generated by analyzing the causes of faults ? thereby making risk analysis possible. It is reported that the analysis data and the evaluation of the risk level are improved, especially for poor location, and that the measurement of Ultra high frequency (UHF) partial discharge of the real live wire in industrial switchgear is spectacular. Partial discharge diagnosis techniques by using the Ultra High Frequency sensor have been recently highlighted, and it is verified by applying them to the GIS. This has become one of the new and various power equipment techniques. Diagnosis using a UHF sensor is easy to measure, and waveform analysis is already standardized, due to numerous past case experiments. This technique is currently active in research and development, and commercialization is becoming a reality. Another aspect of this technique is that it can determine the occurrences and types of partial discharge, by the application diagnosis for live wire of ultra high voltage switchgear. Measured data by using the UHF partial discharge techniques for ultra high voltage switchgear was obtained from 200 places in Gumi, Yeosu, Taiwan and China's semiconductor plants, and also the partial discharge signals at 15 other places were found. It was confirmed that the partial discharge signal was destroyed by improving the work of junction bolt tightening check, and the cable head reinforcement insulation at 8 places with a possibility for preventing the interruption of service. Also, it was confirmed that the UHF partial discharge measurement techniques are also a prevention diagnosis method in actual industrial sites. The measured field data and the usage of the research for risk assessment techniques of the live wire status of power equipment make a valuable database for future improvements.

Keywords

References

  1. A. G. Sellars, O. Farish, and B. F. Hampton, IEEE Trans. on Dielectr. Electr. Insul., 323 (1994) [DOI: http://dx.doi.org/10.1109/94.300265].
  2. B. F. Hampton and R. J. Meats, IEE Proceedings C, 137 (1988) [DOI: http://dx.doi.org/10.1049/ip-c.1988.0017].
  3. J. S. Pearson, O. Farish, B. F. Hampton, M. D. Judd, D. Templeton, B. M. Pryor, and I. M. Welch, IEEE Trans. Dielectr Electr. Insul., 893 (1995) [DOI: http://dx.doi.org/10.1109/94.469984].
  4. J. Y. Lim and J. Koo, J. Kor. Phys. Soc., 755 (2003).
  5. M. D. Judd, O. Farish, B. F. Hampton, IEEE Trans. On DEI., 213 (1996).
  6. N. Kock, B. Cornic, and R. Pietsch, IEEE Electr. Insul. Magazine, 20 (1996).
  7. Koo, J. Yoon, J. Lim, Y. Chang , and Y. Kang, C, 335 (ISH. 2003).
  8. Micro Wave Studio V5.0 (Computer Simulation Technology, 2004).
  9. H. Doi, H. Muto, M. Fujii, and H. Kamei, Proc. IEE High Voltage Engineering Symposium, 70 (1999).
  10. M. D. Judd, in "Dielectric Windows Improve Sensitivity of Partial Discharge Detection at UHF" (Conference Record of the 2000 IEEE International Symposium on Electrical Insulation, CA USA, 2000).
  11. L. Yang, B. G. Stewart, A. J. Reid, M. D. Judd, and R. A. Fouracre, in "Proceeding of the 14th International Symposium on High Voltage Engineering" (Tsinghua University, Beijing, 2005) p. 347.
  12. S. Y. Jung, J. Y. Koo, Y. M. Jang, K. J. Park, and C. W. Kang, in "Proceeding of the 14th International Symposium on High Voltage Engineering" (Tsinghua University, Beijing, 2005) p. 382.
  13. Suwarno and T. Mizutani, in "Proceeding of 2008 International Conference on Condition Monitoring and Diagnosis" (North China Electric University, Beijing, 2008) p. 60.
  14. S. G. Goo, H. J. Ju, K. J. Park, K. S. Han, and J. Y. Yoon, in "Proceeding of 2008 International Conference on Condition Monitoring and Diagnosis" (North China Electric University, Beijing, 2008) p. 64.

Cited by

  1. Comparison of Partial Discharge Characteristics in SF6Gas Under AC and DC vol.16, pp.6, 2015, https://doi.org/10.4313/TEEM.2015.16.6.323
  2. Analysis of PD Signal for Condition Monitoring of MV Switchboards by the Measurement of Transient Earth Voltage vol.19, pp.3, 2018, https://doi.org/10.1007/s42341-018-0037-5