DOI QR코드

DOI QR Code

서버 컴퓨터의 발열량이 변화한 경우의 데이터센터 내의 기류 및 온도분포 특성에 대한 연구

A Study on the Distribution of Airflow and Temperature in a Data center under the Various Conditions of Heat Generation Rates of Server Computers

  • 장현재 (홍익대학교 건축공학부) ;
  • 김제영 (홍익대학교 대학원 건축공학과)
  • Chang, Hyun-Jae (School of Architectural Engineering, Hongik University) ;
  • Kim, Je-Young (Graduate School of Architectural Engineering, Hongik University)
  • 투고 : 2013.12.27
  • 심사 : 2014.02.03
  • 발행 : 2014.03.10

초록

On a large scale of data center, heat generation rates from sever computers occupy almost the entire cooling load of the building, and it is gradually increasing. The efficiency of air distribution system in data centers can be affected by heat generation rates of server computers. In this study, the distributions of airflow and temperature in a data center have been investigated by CFD simulations under various conditions of heat generation rates for server computers. From the results, air around the cold aisle which has high temperature flows tremendously into the cold aisle according to the increase of heat generation rates for server computers and the air temperature in the cold aisle becomes higher. The SHI (supply heat index) and RHI (return temperature index) show almost similar values to the cases study because the air inflow rates to server computers increase with the heat generation rates of server computers.

키워드

참고문헌

  1. Datacom equipment power trends and cooling applications, ASHRAE, 2012, p. 34.
  2. Datacom Equipment Power Trends and Cooling Applications, 2012, ASHRAE, pp. 29-39.
  3. Chang, H. J., Jung, Y. H., and Seo, J, H., 2013, A study on the methodology of simulation on the distribution of airflow and temperature in a date center by utilizing porous boundary condition, J. of KIAEBS, KIAEBS, pp. 289-294.
  4. ANSYS FLUENT MANUAL, ANSYS.
  5. Sharma, R. K., Bash, C. E., and Patel, C. D., 2002, Dimensionless parameters for evaluation of thermal design and performance of large scale data centers, Proceedings of AIAA 2002-3091, American Institute of Aeronautics and Astronautics Conference.
  6. Cho, J. K. and Kim, B. S., 2011, Evaluation of air management system's thermal performance for superior cooling efficiency in highdensity data centers, Energy and Buildings, pp. 2145-2135.

피인용 문헌

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380