An Analytical Study on Indoor Thermal Comfort Performance According to the Automatic Control of Internal-External Blind

  • Lee, Do-Hyung (Dept. of Architecture, Hanbat National University) ;
  • Kim, Tae-Woo (Dept. of Architecture, Hanbat National University) ;
  • Yoon, Jong-Ho (Dept. of Architecture, Hanbat National University)
  • Received : 2014.05.07
  • Accepted : 2014.06.05
  • Published : 2014.06.30

Abstract

The purpose of this study is to analyse PMV (Predicted Mean Vote) and PPD (Predicted Percentage of dissatisfied) by automatic control of slat-type vertical blind. EnergyPlus, a building energy analysis software has been used for this study. The energy model is calibrated in Energy Plus using measured zone temperature and glass surface temperature data for one day and thermal comfort performance inside the building analysis was carried out. The calibrated data has the MBE of 4% and Cv(RMSE) of 10%. The result was that, for better zone thermal comfort, installation of blind on the outside is more appropriate than inside or no blind case. Additionally, different glazing types were compared and it was found that Triple Low-e glass is the most favorable.

Keywords

References

  1. ISO Standard 7730, 2005
  2. P.O. Fanger, Thermal Comfort, McGraw-Hill Book CO., 1970
  3. The U.S. DOE, EnergyPlus Input Output Reference. The Encyclopedic Reference to EnergyPlus Input and Output, 2011
  4. F. Winkelmann, Modeling Windows in EnergyPlus, Building simulation 2011 in : 7th international IBPSA Conference, 2011. 9
  5. The U.S. DOE, EnergyPlus Engineering Reference, 2011
  6. ISO 15099, Thermal Performance of Windows, Doors, and Shading Devices-Detailed Calculations, International Organization for Standardization, 2003
  7. The U.S. DOE, M&V guidelines, Measurement and verification for federal energy projects version 3.0, 2008
  8. The U.S. DOE, Lawrence Berkeley National Laboratory, Tips &Tricks for Using EnergyPlus, 2012
  9. ANSI/ASHRAE Standard 55-2010, Thermal Environmental Conditions for Human Occupancy, 2010
  10. Korea Institute of Energy Research, Result spread of energy business, 2007
  11. Yoon Yeo Beom, Kim Dong Su, Lee Kwang Ho, A study on the building energy performance depending on the blind location, blind operation and glazing type, Architectural Institute of Korea, 2013
  12. Myung Hwan Oh, Kwang Ho Lee, Jong Ho Yoon, Automated Control Strategies of Inside Slat-type Blind Considering Visual Comfort and Building Energy Performance, Energy and Buildings, 2012
  13. Lee Yong Jun, Shin Jee Woong, Lee Yun Gyu, Lee Kyung Hoi, The methods to improve thermal environment of a room adjacent to an external unit room for high-rise apartment buildings, Korea Institute of Ecological Architecture and Environment, 2005
  14. Kim Se Hyun, Noh Kwang Chul, Oh Myung Do, Study on the evaluation method of thermal comfort in consideration of the indoor radiation load, The Society of Air-conditioning and Refrigerating Engineers of Korea, 2003
  15. Mo Paek Hyoun, Kang Dong Hwa, Choi Dong Hee, Sun Jong Myung, Yeo Myoung Souk, Kim Kwang Woo, Study on thermal comfort and energy consumption characteristic in PMV controlled space, Korean Institute of Architectural Sustainable Environment and Building Systems, 2008
  16. Noh Kwang Chul, Oh Myung Do, Comparison of thermal comfort performance indices for cooling loads in the lecture room, The Korean Society of Mechanical Engineers, 2005
  17. Hwang Deuk Soo, Lee Kyung Hee, A study on the change of indoor thermal environment according to the location of blinds, The Korean Solar Energy Society, 2011
  18. Yoon Yeo Beom, Lee Kwang Ho, An experimental study on the indoor environment assessment under the automated exterior blind operation, Architectural Institute of Korea, 2013
  19. Yoon Kap Chun, Kim Kang Soo, An evaluation of energy performance in an office with venetian blinds in summer, Architectural Institute of Korea, 2012
  20. Kim Dong Kyun, Yoon Kap Chun, Kang Jae Sik, Kim Kang Soo, An experimental study on indoor thermal characteristics in accordance with the use of windows and blinds in double skin facade in summer, The Korean Solar Energy Society, 2011
  21. Jeong Woo Ram, Oh Myung Hwan, Lee Kwang Ho, Yoon Jong Ho, Evaluation of thermal environment by installing the indoor roll blind in the office building, Korean Institute of Architectural Sustainable Environment and Building Systems, 2012