Membrane backwashing waste shows seasonally different characteristics and it has bad settleability differently from general backwashing waste in water treatment plant. When chemicals was injected to membrane backwashing waste, the settleability was better than chemicals was not injected. However, when settled lower sludge was not discharged, flowing sludge continuously was concentrated over a certain surface and floatation penomena occurred according to flowing velocity. When the lower sludge was discharged continuously in the thickener to prevent floatation penomena of turbidity materials, the depth of sludge surface was the least and the settleability increased.

Keywords

References

  1. Bae, B.U. and Choi, K.H. (2012) Design of Residual Treatment Process with Filter Backwash Recycle System, Journal of Korean Society on Water Environment(KSWE), 28 (1), 109 - 114.
  2. Bae, B.U. and Shen, X.H. (2009) Thickening Characteristics of Residual from a Ceramic Membrane Water Treatment Plant, Journal of Korean Society on Water Environment (KSWE), 25(5), 764 - 767.
  3. Balasubramanian, P. (2013) A Brief Review on Best Available Technologies for Reject Water(brine) Management in Industries, International Journal of Environmental Sciences, 3(6), 2010 - 2018.
  4. Chung, P.G., Kwak, D.H., Lee, E.J. and Kim, Y.C. (1997) Floatation-like Phenomena in Water Treatment Processes adopted Conventional Gravity Sedimentation, Journal of Korean Society of Environmental Engineers, 19(11), 1465 - 1474.
  5. Kwak, J.W. (1998) Physical-Chemical Principle and Practice of Water Treatment. p.493, Ji-Sam, Seoul.
  6. K-water Institute (2011) Water Treatment Engineer Comprehensive.
  7. Ministry of Environment (2012) Standards for the Installation of Membrane Filtration Water Treatment Facilities.
  8. Moon, Y.T., Seo, I.S., Kim, H.S., Park, N.S. and Ahn, H.W. (2006) Evaluation of Design Parameter on Residual Treatment Facilities in Membrane Water Treatment Plants, Journal of the Korean Society of Water and Wastewater, 20(1), 138 - 146.
  9. Tom, D.R. and Paul, A.R. (1995) Unit Operations and Processes in Environmental Engineering. 2nd Ed. p. 219-239, PWS Publishing Company, Boston.