DOI QR코드

DOI QR Code

내부 열교환기를 이용한 R-1270용 냉동시스템의 성능 분석

Performance Analysis of R-1270(Propylene) Refrigeration System Using Internal Heat Exchanger

  • 구학근 (동명대학교 냉동공조공학과)
  • Ku, Hak-Keun (Department of Refrigeration and Air Conditioning Engineering, TongMyong University)
  • 투고 : 2014.05.13
  • 심사 : 2014.05.30
  • 발행 : 2014.08.31

초록

This paper considers the influence of internal heat exchangers on the efficiency of a refrigerating system using R-1270. These internal heat exchangers(liquid-gas or suction-line heat exchangers) can, in some cases, yield improved system performance while in other cases they degrade system performance. A steady state mathematical model is used to analysis the performance characteristics of refrigeration system with internal heat exchanger. The influence of operating conditions, such as the mass flowrate of R-1270, inner diameter tube and length of internal heat exchanger, to optimal dimensions of the heat exchanger is also analyzed. The main results were summarized as follows : the mass flowrate of R-1270, inner diameter tube and length of internal heat exchanger, and effectiveness have the influences on the cooling capacity, compressor work and RCI(Relative Capacity Index) of this system. With a thorough grasp of it is possible to design the R-1270 compression refrigeration cycle using internal heat exchanger.

키워드

참고문헌

  1. R. N. Richardson and J. S. Butterworth, 1995, "The performance of propane/isobutane mixtures in a vapour-compression refrigeration system", Int. J. Refrigeration, Vol. 18, No. 1, pp. 58-62. https://doi.org/10.1016/0140-7007(94)P3712-A
  2. M. Y. Wen and C. Y. Ho, 2005, "Evaporation heat tranfer and pressure drop characteristics of R-290(propane), R-600(butane), and a mixture of R-290/R-600 in the three-lines serpentine small-tube bank", Applied Thermal Engineering, Vol. 25, pp. 921-936.
  3. J. H. Hwang, I. C. Baek and D. S. Jung, 2006, "Performance of HCFC22 alternatives R1270, R290, R1270/R290, R290/HFC152a, R1270/R290/RE170 refrigerants for air-conditioning and heat pump applications", SAREK, Vol. 18, No. 4, pp. 312-319.
  4. H. M. Jeong et al, 2007, "The Characteristic of Propane(R-290)-Ethane(170) as Refrigerant in the Cascade Refrigeration System", Journal of the Korea Society for Power System Engineering, Vol. 11, No. 4, pp. 50-55.
  5. H. K. Oh and C. H. Son, 2012, "Performance analysis of R410A refrigeration system using as secondary refrigerant", Journal of the Korea Society for Power System Engineering, Vol. 16, No. 2, pp. 24-29.
  6. W. F. Stoecker and D. J. Walukas, 1981, "Conserving energy in domestic refrigerators through the use of refrigerant mixture", ASHRAE Transactions, Vol. 87, No. 1, pp. 279-281.
  7. M. O. McLinden, 1990, "Optimum refrigerants for non-ideal cycles: an analysis employing corresponding states", In:Proceedings ASHRAE-Purdue CFC and IIR-Purdue Refrigeration Conferences, W. Lafayette (IN), pp. 17-20.
  8. P. A. Domanski and D. A. Didion, 1993, "Thermodynamic evaluation of R22 alternative refrigerants and refrigerant mixtures", ASHRAE Transactions, Vol. 99, No. 2, pp. 636-648.
  9. P. A. Domanski, D. A. Didion, J. P. Doyle, 1994, "Evaluation of suction-line/ liquid-line heat exchange in the refrigeration cycle", Rev Int Froid, Vol. 7, No. 7, pp. 487-93.
  10. S. A. Klein and F. L. Alvarado, 1998, EES-engineering equation solver. 4406 Fox Bluff Rd, Middleton(WI 53562):F-Chart Software.

피인용 문헌

  1. A Study on the Refrigerant Distributor Design on the Reduced Diameter of Evaporator in the Air Conditioner vol.23, pp.3, 2019, https://doi.org/10.9726/kspse.2019.23.3.082
  2. Performance Analysis of R290 (propane) Refrigeration System Using Liquid-gas Heat Exchanger vol.23, pp.4, 2014, https://doi.org/10.9726/kspse.2019.23.4.091