DOI QR코드

DOI QR Code

Utilization of Heat from Waste-Incineration Facility for Heating Large-Scale Horticultural Facilities

소각시설 여열을 이용한 대규모 시설원예 단지의 난방 시스템 적용 가능성 평가

  • Lee, Jaeho (Graduate School, Hanbat National University) ;
  • Hyun, Intak (Graduate School, Hanbat National University) ;
  • Lee, Kwang Ho (Department of Architectural Engineering, Hanbat National University)
  • 이재호 (한밭대학교 대학원 건축공학과) ;
  • 현인탁 (한밭대학교 대학원 건축공학과) ;
  • 이광호 (한밭대학교 건축공학과)
  • Received : 2015.05.27
  • Accepted : 2015.06.23
  • Published : 2015.08.10

Abstract

The Korean government plans to establish large-scale horticultural facilities using reclaimed land to improve the competitiveness of the national agricultural sector at the government level. One of the most significant corresponding problems is the ongoing dependence of these facilities on fossil fuel, whereby constant heating is necessary during the winter season to provide the necessary breeding conditions for greenhouse crops. In particular, high-level energy consumption is incurred from the use of heating-related coverings with large heat-transmission coefficients such as those composed of vinyl and glass. This study investigated the potential applicability of waste-incineration heat for use in large-scale horticultural facilities by evaluating the hot-water temperature, heat loss, and available greenhouse area as functions of the distance between the incineration facility and the greenhouse. In conclusion, waste-incineration heat from a HDPE pipe can heat a horticultural facility of 10 ha if the distance is less than 8 km.

Keywords

References

  1. Ministry of Knowledge Economy, 2009, The Third District Energy Supply Plan.
  2. Ministry of Agriculture, Food and Rural Affairs, 2009, Framework for Large-scale Reclamation Site Usage Plan.
  3. Ministry of Agriculture, Food and Rural Affairs, Plan for Utilization of Large-scale Reclaimed Land Area
  4. Hyun, I. T., Lee, J. H., Yoon, Y. B., Nam, Y. J., Lee, K. H., 2014, The Potential and Utilization of Unused Energy Sources for Large-Scale Horticulture Facility Applications under Korean Climatic Conditions, Energies, Vol. 7, No. 8, pp. 4781-4801. https://doi.org/10.3390/en7084781
  5. Lee, J. H., Hyun, I. T., Yoon, Y. B., Nam, Y. J., and Lee, K. H., 2015, Energetic and Economic Assessment of Pipe Network Effects on Unused Energy Source System Performances in Large-scale Horticulture Facilities, Energies, Vol. 8, No. 5, pp. 3328-3350. https://doi.org/10.3390/en8053328
  6. Chin, D. H., 2009, A study on expanding the practical use of energy by using the remaining heat of incinerator, PhD's Dissertation, Yeungnam University, Gyeongsan, South Korea.
  7. Lee, J. H., Hyun, I. T., Kim, H. W., and Lee, K. H., 2015, Applicability of Waste Heat from Incineration Facility for Large-scale Horticulture Facilities, In Proceedings of the Summer Conference of the Society of Air-Conditioning and Refrigerating Engineers of Korea(SAREK), Youngpyong, South Korea, pp. 699-702.
  8. Crawley, D. B., Lawrie, L. K., Winkelmann, F. C., Buhl, W. F., Huang, H. J., Pedersen, C. O., Strand, R. K., Liesen, R. J., Fisher, D. E., Witte, M. J., and Glazer, J., 2001, EnergyPlus : Creating a New-generation Building Energy Simulation Program. Energy and Buildings, Vol. 33, No. 4, pp. 319-331. https://doi.org/10.1016/S0378-7788(00)00114-6
  9. ASHRAE Fundamentals Handbook, 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
  10. EnergyPlus. Testing and Validation, http://apps1.eere.energy.gov/buildings/energyplus/testing.cfm.
  11. Kim, Y. H., 2007, study of geothermal heat pump performance prediction and assessment technique, PhD's Dissertation, Jeju National University, Jeju, South Korea.
  12. Choi, S. W., 2012, A study on thermal conductivity characteristics of deep depth vertical closed-loop ground heat exchanger, Master's Thesis, KwangWoon Univercity, Seoul, South Korea.
  13. Standard Test Method for Determining Air Leakage Rate by Fan Pressurization, Active Standard No ASTM E 779-87, American Society for Testing and Materials (ASTM). 1987.
  14. Kim, K. S., Yoon, J. H., and Song, I. C., 2000, Energy Performance Evaluation of Heat Reflective Radiant Barrier Systems for Greenhouse Night Insulation. Journal of Architectural Institute of Korea, Vol. 16, No. 10, pp. 153-161.
  15. Lee, K. H. and Strand. R. K., 2006, Implementation of an Eerth Tube System Into EnergyPlus Program. SimBuild 2006, The 2nd National Conference of IBPSA-USA, Cambridge, MA, USA.

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2015 vol.28, pp.6, 2016, https://doi.org/10.6110/KJACR.2016.28.6.256