DOI QR코드

DOI QR Code

Voltage Control of Stand-Alone Inverter for Power Quality Improvement Under Unbalanced and Non-linear Load

불평형 및 비선형부하 시 전력품질 향상을 위한 독립형 인버터의 전압제어 기법

  • Lee, Wujong (Hanwha Corporation R&D Center) ;
  • Jo, Jongmin (Dept. of Electrical Engineering, Chungnam National Univ.) ;
  • Cha, Hanju (Dept. of Electrical Engineering, Chungnam National Univ.)
  • Received : 2015.09.22
  • Accepted : 2016.02.23
  • Published : 2016.04.01

Abstract

This paper proposed the voltage control of stand-alone inverter for power quality improvement under unbalanced and non-linear load. The 3-phase DC-AC inverter controls CVCF(Constant Voltage Constant Frequency) and selective harmonic eliminate method in stand-alone mode by PR controller, and the stand-lone inverter supplies stable sinusoidal voltage to balanced, unbalanced and non-linear loads. The total harmonic distortion(THD) of line-to-line load voltage($V_{LL}$) is 1.2% in the balanced load. THD of $V_{LL}$ is reduced from 5.2% to 1.4% and 6.7% to 3.5%, respectively unbalanced and non-linear load. The stand-alone inverter can be supplies sinusoidal balanced voltage to unbalanced load because the voltage unbalanced factor(VUF) of $V_{LL}$ is reduced from 5.2% to 1.4% in the unbalanced load. Feasibility of control method for a stand-alone inverter will be verified through 30kW stand-alone inverter system.

Keywords

References

  1. Farid Katiraei, Reza Iravbani, Nikos Hatziarhyriou and Aris Dimeas "Microgirds Management : Controls and Operation Aspects of Microgirds", IEEE Power &Energy Magazine, may/june 2008.
  2. P. Bauer, Leake E. Weldemariam and Evert Raijen, "Stand-alone Microgrids", IEEE Telecommunications Energy Conference (INTELEC), pp. 1-10, October 2011.
  3. Xisheng Tang, Wei Deng and Zhiping Qi, "Investigation of the Dynamic Stability of Microgrid", IEEE Trans. on Power Systems, Vol. 29, No. 2, pp. 698-706, March 2014. https://doi.org/10.1109/TPWRS.2013.2285585
  4. R. Lasseter, Abbas Akhil, Chris Marnay, John Stevens, Jeff Dagle, Ross Guttromson, A. Sakis Meliopoulous, Robert Yinger and Joe Eto, "White Paper on Integration of Distributed Energy Resources-The CERTS Microgrid Concept", Office of Power Technologies of the IS Department of Energy, April 2002.
  5. Remus Teodorescu, Marco Liserre, Pedro Rodriguez "Grid Converters for Photovoltaic and Wind Power Systems", WILEY IEEE, 2011.
  6. P. Li, B. Dan, K. Yong, and C. Jian, "Research on three-phase inverter with unbalanced load," Paper presented at APEC2004 Conference on February 22-26, 2004. Anaheim, California, Conf., pp. 128-133, Feb. 2004.
  7. Jong-Woo Choi and Seung-Ki Sul, "Inverter Output Voltage Synthesis Using Novel Dead Time Compensation", IEEE Trans. on Power Electronics, Vol. 11, No. 2, pp. 221-227, 1996, March. https://doi.org/10.1109/63.486169
  8. T. K. Vu, S. H. Lee, and H. J. Cha, "A new on-line dead-time compensator for single-phase PV inverter," Transactions of Korean Institute of Power Electronics, Vol. 17, No. 5, pp. 569-576, Oct. 2012.
  9. 김종겸, 이은웅, "불평형 전압으로 운전시 비선형 부하에 나타나는 현상", 대한전기학회 논문지, Vol. 51, No. 6, pp. 285-291, 2002.6
  10. 김종겸, 이은웅, 이동주, "불평형 전압으로 운전하는 비선형 부하의 고조파 특성분석", 대한전기학회 논문지, Vol. 52B, No. 10, pp. 491-500, 2003.10
  11. D. W. P. Thomas and M. S. Woolfson, "Evaluation of frequency tracking methods", IEEE Trans. Power Delivery, Vol. 16, Issue 3, pp.367-371, July 2001.
  12. V. Blasko and V. Kaura, "Operation of a Phase Locked Loop System under Distorted UItility Conditions", IEEE Trans. on Industrial Electronics, Vol. 33, No. 1, pp 58-63, January/February 1997.
  13. Erika Twining and Donald Grahame Holmes, "Grid Current Regulation of a Three-Phase Voltage Source Inverter With an LCL Input Filter", IEEE Trans. on Power Electronics, Vol. 18, No. 3, pp. 888-895, May 2003.
  14. Trung-Kien Vu, "Power Quality Improvement of Single-Phase Grid-Connected Photovoltaic Inverter" Ph.D thesis, Chungnam National University, February 2011.
  15. 김종겸, 박영진, 이은웅, "선간전압과 상전압에 대한 전압 불평형율의 비교", 대한전기학회 논문지, Vol. 54B, No. 9, pp 403-407, 2005.9