DOI QR코드

DOI QR Code

Output Control of Wind Farm Side Converter from DC Link for DC Voltage Stabilization with HVDC

해상풍력 연계용 HVDC의 DC전압 안정화를 위한 DC Link의 발전기측 컨버터 제어 전략

  • Received : 2016.04.07
  • Accepted : 2016.08.30
  • Published : 2016.09.01

Abstract

This paper presents DC voltage recovery time improvement method in DC link of High Voltage Direct Current (HVDC) with offshore wind farm. The wind farm should be satisfied Low Voltage Ride Through(LVRT) control strategy when grid faults occur. The LVRT control strategy indicates actions which have to be executed according to the voltage dip ratio and the fault duration. However, The LVRT control strategy makes between wind farm and power system through DC Link voltage when grid fault occurs. The de-loading scheme is one of the method to control the DC voltage. But de-loading scheme need to long DC voltage recovery time. Thus, this paper proposes an improved de-loading scheme and we analysis DC voltage and active power reference through a simulation.

Keywords

References

  1. "The Global Wind Energy Council News", GWEC, September 2014.
  2. D. B. Nah, H. S. Shin, D. J. Nah, "Trends in offshore wind power technologies", Journal of Energy Engineering, Vol. 20, No. 2, pp. 143-153, 2011. https://doi.org/10.5855/ENERGY.2011.20.2.143
  3. T. Ackermann, "Wind Power in Power System", John Wiley & Sons, pp. 53-95, 2005.
  4. "Grid Code for High and Extra High Voltage", E. ON Netz GmbH, 2006.
  5. C. Abbey, "Effect of low voltage ride through (LVRT) characteristic on voltage stability", IEEE Power Engineering Society General Meeting, pp. 1901-1907, June 2005.
  6. P. Breseti, W. L. Kling, R. L. Hendriks, R. V, "HVDC connection of offshore wind farms to the transmission system", IEEE Transactions on Energy Conversion, Vol. 22, No. 1, pp. 37-43, March 2007. https://doi.org/10.1109/TEC.2006.889624
  7. G. Ramtharan, A. Arulampalam, J. B. Ekanayake, F. M. Hughes, N. Jenkins, "Fault ride through of fully rated converter wind AC and DC transmission systems", IET Renew. Power Gener., Vol. 3, No. 4, pp. 426-438, 2009. https://doi.org/10.1049/iet-rpg.2008.0018
  8. H. S. Lee, "LVRT control of full scale wind power system by means of PMSG", a Master's Thesis, Graduate School of Electrical Engineering, Korea University, 2013.
  9. G. T. Son, H. J. Lee, T. S. Nam, Y. H. Chung, U. H. Lee, S. T. Baek, K. Hur, J. W. Park, "Design and control of a modular multilevel HVDC converter with redundant power modules for noninterruptible energy transfer", IEEE Transactions on Power Delivery, Vol. 27, No. 3, pp. 1611-1619, July 2012. https://doi.org/10.1109/TPWRD.2012.2190530
  10. M. Saeedifard, R. Iravani, "Dynamic performance of a modular multilevel back-to-back HVDC system", IEEE Transactions on Power Delivery, Vol. 25, No. 4, pp. 2903-2912, October 2010. https://doi.org/10.1109/TPWRD.2010.2050787
  11. J. S. Huh, S. I. Park, D. H. Kim, and J. C. Kim, "The effect of AC grid phase to ground fault on DC voltage of modular multi-level converter HVDC for wind farm", KIEE Summer Annual Conference, pp. 294-295, July 2014.
  12. P. Bjorklund, P. Jiuping, Y. Chengyan, K. Stivastava, "A new approach for modeling complex power system components in different simulation tools", Power System Computation Conference (PSCC), 2008.
  13. A. Yazdani, R. Iravani, "Voltage-sourced converters in power system modeling control, and Applications", Wiley, 2010.
  14. P. Kundur, "Power System Stability and Control". McGraw-Hill, 1994.
  15. J. S. Huh, W. S. Moon, S. I. Park, D. H. Kim, J. C. Kim, "DC-link voltage control of HVDC for offshore wind farm using improved de-loading method", The Transactions of the Korean Institute of Electrical Engineers(KIEE), Vol. 64, No. 3, pp. 399-404, 2015. https://doi.org/10.5370/KIEE.2015.64.3.399