DOI QR코드

DOI QR Code

MMC 기반 STATCOM 용 밸브의 성능시험 장치를 위한 새로운 토폴로지

New Topology for Valve Performance Test Equipment of MMC based STATCOM

  • 투고 : 2016.11.26
  • 심사 : 2016.12.28
  • 발행 : 2017.02.20

초록

This study proposes a new topology for the performance test of a valve consisting of a modular multilevel converter (MMC)-based static synchronous compensator (STATCOM). The conventional valve performance test equipment requires high-voltage AC source of several kV rating because the number of submodules to be tested in a valve should be at least six or eight. However, the power source of the proposed scheme is DC and not AC source. The DC power source voltage range of the proposed test circuit is from several volts to several tens of volts. Therefore, the size and cost for the performance test equipment can be reduced considerably compared with the conventional method. The proposed scheme satisfies the requirements of the IEC 62927 standard. Simulations are conducted for a valve of 50[MVA] MMC-based STATCOM. Experimental results with a scale-downed setup show the validity of the proposed performance test topology.

키워드

참고문헌

  1. C. Duan, W. Fang, L. Jiang, and S. Niu, "FACTS devices allocation via sparse optimization," IEEE Transactions on Power Systems, Vol. 31, No. 2, pp. 1308-1319, Mar. 2016. https://doi.org/10.1109/TPWRS.2015.2433891
  2. M. Sahraei-Ardakani and S. A. Blumsack, "Transfer capability improvement through market-based operation of series FACTS devices," IEEE Transactions on Power Systems, Vol. 31, No. 5, pp. 3702-3714, Sep. 2016. https://doi.org/10.1109/TPWRS.2015.2508720
  3. C. K. Lee, J. S. K. Leung, S. Y. R. Hui, and H. S. H. Chung, "Circuit-level comparison of STATCOM technologies," Journal of Power Electronics, Vol. 18, No. 4, pp. 1084-1092, Jul. 2003.
  4. H. Akagi, S. Inoue, and T. Yoshii, "Control and performance of a transformerless cascade PWM STATCOM with star configuration," IEEE Transactions on Industry Applications, Vol. 43, No 4, pp. 1041-1049, Jun./Aug. 2007. https://doi.org/10.1109/TIA.2007.900487
  5. Fang Z. Peng and Jin Wang, "A universal STATCOM with delta-connected cascade multilevel inverter," IEEE PESC'04, pp. 3529-3533, Jun. 2004.
  6. R. E. Betz and T. Summerst, "Using a cascaded h-bridge STATCOM for rebalancing unbalanced voltages," 7th Internatonal Conference on Power Electronics, pp. 1219-1224, Oct. 2007.
  7. J. I. Y. Ota, Y. Shibano, N. Niimura, and H. Akagi, "A phase-shifted-PWM D-STATCOM using a modular multilevel cascade converter (SSBC) - Part I: modeling, analysis, and design of current control," IEEE Transactions on Industry Applications, Vol. 51, No. 1, pp. 279-288, Jan./Feb. 2015. https://doi.org/10.1109/TIA.2014.2326079
  8. IEC Std., "IEC 62927 Ed.1: Voltage sourced converter (VSC) valves for static synchronous compensator (STATCOM) - Electrical Testing," IEC, 2015.