The Effects of Operational Conditions of Cooling Water System on Energy Consumption for Central Cooling System

냉각수 계통의 운전변수가 중앙냉방시스템의 에너지소비량에 미치는 영향

  • 안병천 (가천대학교 기계공학과)
  • Received : 2017.10.18
  • Accepted : 2017.11.21
  • Published : 2017.12.01

Abstract

The effects of operational conditions of cooling water system on energy consumption for central cooling system are researched by using TRNSYS program. Cooling tower water pump flow rate, cooling tower fan flow rate, and condenser water temperature with various dry-bulb and wet-bulb temperatures are varied and their effects on total and component power consumption are studied. If the fan maximum flow rates of cooling tower is decreased, cooling tower fan and total power consumptions are increased. If the cooling tower water pump maximum flow rates is decreased, chiller and total power consumptions are increased. If condenser water set-point temperature is increased, chiller power consumption is increased and cooling tower fan power consumption is decreased, respectively.

Keywords

References

  1. Ahn, B. C., and Mitchell, J. W., 2001, Optimal control development for chilled water plants using a quadratic representation, Energy and Buildings, 33 No. 4, pp. 371-378. https://doi.org/10.1016/S0378-7788(00)00119-5
  2. Hwang, J. W., and Ahn, B. C., 2013, Experimental study on optimal operation strategies for energy saving in building central cooling system, Journal of the Korea Academia-Industrial Cooperation Society, Vol. 14, No. 9, pp. 4610-4615. https://doi.org/10.5762/KAIS.2013.14.9.4610
  3. Kim, Y. I., 2010, Performance of a water cooled chiller by controlling chilled water exit temperature, Proceedings of the SAREK 2010 Summer Annual Conference, pp. 1136-1141.
  4. Rho, J. D., 2014, Optimization of cooling water system, Proceedings of the SAREK 2014 Summer Annual Conference, pp. 575-581.
  5. TRNSYS, 2007, Transient system simulation program Ver. 16.1, Solar Energy Laboratory, University of Wisconsin-Madison.