외기 온도 변화가 핀-관 열교환기의 공기측 열전달계수와 마찰계수에 미치는 영향에 관한 실험적 연구

An Experimental Study on the Effect of the Air Temperature on the Air-Side Heat-Transfer Coefficient and the Friction Factor of a Fin-and-Tube Heat Exchanger

  • 김내현 (인천대학교 기계시스템공학부) ;
  • 조홍기 (삼성전자 생활가전사업부)
  • Kim, Nae-Hyun (Division of Mechanical System Engineering, Incheon National University) ;
  • Cho, Honggi (Digital Appliance Business, Samsung Electronics)
  • 투고 : 2016.11.07
  • 심사 : 2016.12.05
  • 발행 : 2017.04.10

초록

In general, the air-side j and f factors of evaporators or condensers are obtained through single-design tests performed under air-dry and wet-bulb temperatures. Considering that the indoor or outdoor air temperatures vary significantly during the operation of an air conditioner, it is necessary to confirm that the experimentally-obtained j and f factors are widely applicable under variable air conditions. In this study, a series of tests were conducted on a two-row slit-finned heat exchanger to confirm the applicability. The results showed that, for the dry-surface condition, the changes of the tube-side water temperature, water-flow rate, and air temperature had virtually no effect on the air-side j and f factors. For the wet condition, however, the f factor was significantly affected by these changes; contrarily, the j factor is relatively independent regarding this change. The formulation of the possible reasoning is in consideration of the condensation behavior underneath the tube. The wet-surface j and f factors are larger than those of the dry surface, with a larger amount for the f factor.

키워드

참고문헌

  1. Wang, C. C., Webb, R. L., and Chi, K. Y., 2000, Data reduction for air-side performance of fin-and-tube heat exchangers, Exp. Thermal Fluid Sci., Vol. 21, No. 4, pp. 218-226. https://doi.org/10.1016/S0894-1777(00)00005-4
  2. Kim, N. H., Oh, W. K., Cho, J. P., Park, H. Y., and Youn, B., 2003, Data reduction on the air-side heat transfer coefficients of heat exchangers under dehumidifying conditions, Korean J. Air Conditioning Refrigeration, Vol. 15, No. 1, pp. 73-85.
  3. Kim, N. H., 2016, Personal communication with Samsung Electronics.
  4. Mills, A. F., 1995, Basic Heat ad Mass Transfer, Irwin Pub.
  5. ASHRAE Standard 41.1, 1986, Standard Method for Temperature Measurement, ASHRAE.
  6. ASHRAE Standard 41.2, 1987, Standard Method for Laboratory Air-Flow Measurement, ASHRAE.
  7. ASHRAE Standard 41.5, 1975, Standard Measurement Guide, Engineering Analysis of Experimental Data, ASHRAE.
  8. ESDU 98005, 1998, Design and performance evaluation of heat exchangers : the effectiveness and NTU method, Engineering and Sciences Data Unit 98005 with Amendment A, London ESDU International plc., pp. 122-129.
  9. Park, B. B., You, S. M., Yoon, B., and Yoo, K. C., 1997, Experimental study of heat transfer and pressure drop characteristics for flow of water inside circular smooth and micro-fin tubes, Korean J. Air Conditioning Refrigeration, Vol. 9, No. 4, pp. 454-461.
  10. Schmidt, T. E., 1949, Heat transfer calculations for extended surfaces, J. of ASRE, Refrigeration Engineering, Vol. 4, pp. 351-357.
  11. Dittus, F. W. and Boelter, L. M. K., 1930, Heat transfer in automobile radiators of the tubular type, University of California Publications on Engineering, Vol. 2, No. 13, pp. 443-461.
  12. Gnielnski, V., 1976, New equations for heat and madd transfer in turbulent pipe and channel flow, Int. Chem. Eng., Vol. 16, pp. 359-368.
  13. Wang, C. C., Tao, W. H. and Du, Y. J., 2000, Effect of waffle height on the air-side performance of wavy fin-and-tube heat exchangers under dehumidifying conditions, Heat Trans. Eng., Vol. 21, pp. 17-26.
  14. Pirompugd, W., Wongwises, S. and Wang, C. C., 2006, Simultaneous heat and mass transfer characteristics for wavy fin-and-tube ehat exchangers under dehumidifying conditions, Int. J. Heat Mass Trans., Vol. 49, pp. 132-143. https://doi.org/10.1016/j.ijheatmasstransfer.2005.05.043