DOI QR코드

DOI QR Code

Feasibility Study of High-Efficiency Ground Heat Exchanger using Double U-tube through a Real-Scale Experiment

  • Bae, Sangmu (Dept. of Architectural Engineering, Pusan National Univ.) ;
  • Kim, Jaemin (Dept. of Architectural Engineering, Pusan National Univ.) ;
  • Nam, Yujin (Dept. of Architectural Engineering, Pusan National Univ.)
  • Received : 2017.07.24
  • Accepted : 2017.08.18
  • Published : 2017.08.30

Abstract

Purpose: The use of renewable energy system is essential for building energy independence and saving energy consumption in the building sector. Among renewable energy technologies, ground source heat pump(GSHP) system is more energy-efficient and environmental-friendly than other heat source systems due to utilize stable ground heat source. However, the GSHP system requires a high initial installation cost and installation space in limited urban area, so it is difficult to have superiority in the market of heat source system. Therefore, it is necessary to develop the installation method of low-cost and improve system performance. This paper aims to evaluate the performance of double u-tube ground heat exchanger(GHX) and verify system feasibility through real-scale experiment. Method: In this study, the real-scale experiment of vertical closed-type GSHP system was conducted using double u-tube GHX and high-efficiency grout. Through the verification experiment, heat source temperature, heat exchange rate(HER) and seasonal performance factor(SPF) were measured according to the long-term operation. In addition, the feasibility analysis was conducted comparing to the single u-tube system. Result: In the results of experiment, average HER was 136.27 W/m and average SPF was 5.41. Furthermore, compared to the single u-tube, the installation cost of the developed system could be reduced about 70% in the same heating load condition.

Keywords

References

  1. Sohn, Byong-Hu, Performance Analysis of Ground-Coupled Heat Pump System with Slinky-Type Horizontal Ground Heat Exchanger, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol.24, No. 3, 2012
  2. XIang-Ri Kong, Yelin Deng, Linyan Li and Wei-Shem Gong, Experimental and numerical study on the thermal performance of ground source heat pump with a set of designed buried pipes, Vol.114, pp. 110-117, Applied Thermal Engineering, 2017. https://doi.org/10.1016/j.applthermaleng.2016.11.176
  3. Jin Luo, Joachim Rohn, Wei Xiang, Manfred Bayer, Anna Priess, Lucas Wilkmann, Hagen Steger and Roman Zorn, Experimental investigation of a borehole field enhanced geothermal response test and numerical analysis of performance of the borehole heat exchangers, Vol.84, pp. 473-484, Energy, 2015. https://doi.org/10.1016/j.energy.2015.03.013
  4. Yan Shang, Min Dong and Sufen Li, Intermittent Experimental Study of a Vertical Ground Source Heat Pump System, Vol. 136, pp. 628-635, Energy, 2014.
  5. Angelo Zarrella, Giuseppe Emmi and Michele De Carli, A Simulation-based Analysis of Variable Flow Pumping in Ground Source Heat Pump Systems with Different Types of Borehole Heat Exchangers : A Case Study, Vol. 131, pp. 135-150, Energy Conversion and Management, 2017. https://doi.org/10.1016/j.enconman.2016.10.061
  6. Jung, Young-Ju, Jo, Jae-Hun, Kim, Yong-Sik and Cho, Young-hum, A Study on the Geothermal Heat Pump System Performance Analysis according to Water Flow Rate Control of the Geothermal Water Circulation Pump, Journal of the Korean Solar Energy Society, Vol. 34, No. 6, pp. 103-109, 2014 https://doi.org/10.7836/kses.2014.34.6.103
  7. Ahn, Byung-Chun, Kim, Jae-Wan and Yong-Sik, Cho, Young-hum, An Experimental Study on the Cooling Operation Characteristics for Different Entering Water Temperatures in Geothermal Heat Pump System, Transactions of the Korean Society of Geothermal Energy Engineers, Vol. 6, No. 1, pp. 1-7, 2010
  8. Hong, Boo-Pyo and Choi, Kwang-Hwan, Experimental Study on the Cooling Performance of Vertical Closed Loop Water to Water Ground Source Heat Pump System, Journal of the Korean Solar Energy Society, Vol. 34, No. 1, pp. 58-63, 2014 https://doi.org/10.7836/kses.2014.34.1.058
  9. Sohn, Byong-Hu, Jung, Kyung-Sik and Choi, Hang-Seok, Performance Prediction of Geothermal Heat Pump(GHP) System using Cast-in-Place Energy Piles, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 25, No. 1, pp. 28-36, 2012
  10. Lim, Kyoung-Bin, Lee, Chang-Hee and Soung, Nak-Won, An Experimental Study on the Thermal Performance Measurement of Vertical Borehole Heat Exchanger(BHE), Transaction of the Korean Society of Mechanical Engineers - B, Vol. 30, No. 8, pp. 764-771, 2006 https://doi.org/10.3795/KSME-B.2006.30.8.764
  11. Cha, Dong An, Kwon, Oh Kyung and Park, Cha Sik, A Study on Heating Characteristics of Ground Source Heat Pump with Variation of Heat Exchange Methods, Transactions of the Korea society Geothermal Energy Engineers, Vol. 8, No. 2, pp. 9-15, 2012
  12. Shintaro Ikeda, Wonjun Choi and Ryozo Ooka, Optimization Method for Multiple Heat Source Heat Pump considering Dynamic variation in Ground Temperature, Vol. 193, pp. 466-478, Applied Energy, 2017. https://doi.org/10.1016/j.apenergy.2017.02.047
  13. Min, Kyong Chon and Choi, Jae Ho, Effect of the Design Parameters of Geothermal Heat Exchanger Design Length, Transactions of the Korea society of Geothermal Energy Engineers, Vol. 2, No. 2, pp. 10-15, 2011
  14. Reddy, T. Agami, Kreider, Jan F., Curtiss, Peter S. and Rabl, Ari, Heating and Cooling of Buildings Design for Efficiency, CRC press Taylor & Francis Group, 2014
  15. Nam, Yujin, Oh, Jin Hwan, Study on the Characteristic of Heat Exchanger for Vertical Geothermal System using the Numerical Simulation, Journal of the Korean Solar Energy Society, Vol. 34, No. 2, pp. 66-72, 2014 https://doi.org/10.7836/kses.2014.34.2.066
  16. Base Price of new & Renewable Energy Source, Korea Energy Agency Korea New & Renewable Energy Center, 2012
  17. Standard of Heating Load Unit, Design Criteria of Heat Energy Usage, Korea District Heating Corporation, 2012