DOI QR코드

DOI QR Code

MEAC Method for Analysis of Power System Stability Improving Effect Considering Run-up SPS Function of HVDC

MEAC를 적용한 HVDC Run-up SPS의 안정도향상 효과분석

  • Lee, Jae-Gul (Power Transmission Lab. KEPCO Research Institute) ;
  • Song, Ji-Young (Power Transmission Lab. KEPCO Research Institute) ;
  • Jang, Gil-Soo (Dept. of Electrical Engineering, Korea University)
  • Received : 2017.04.13
  • Accepted : 2017.09.12
  • Published : 2017.10.01

Abstract

In spite of continuous increase of electric power demand and new generation plants, it is very difficult to install new transmission line. Therefore, it comes to be difficult to operate the power system stable, so it is required to find another way to get new transmission capacity. Because HVDC transmission system installation is the one of the best option for us, we have undertake the HVDC project in mainland. Buckdangjin-Goduck HVDC project(500kV, 3GW) is currently under construction and Eastern Power HVDC project(500kV, 8GW) is under the study for technical specification. Both of them have the Run-up SPS function for taking action of 765kV Transmission line fault. The Run-up SPS function increases the active power output of the HVDC rapidly when the transmission line between the power plant and network is tripped, thereby preventing the generator from overspeed and improving the power system stability. In this paper, we propose MEAC(Modified Equal Area Criteria) method based on traditional EAC method to quantitatively evaluate the effect of the HVDC run-up SPS function on the power system stability improvement.

Keywords

References

  1. P. M. Anderson, B. K. LeReverend: "Industry Experience with Special Protection Schemes", IEEE Transactions on Power Systems, Vol. 11, No. 3, August 1996.
  2. P. Kundur, Power System Stability and Control, McGraw-Hill, 1993.
  3. M. H. Haque, "Evaluation of First Swing Stability of a Large Power System With Various FACTS Devices", IEEE Transactions on Power Systems, Vol. 23, No. 3, August 2008.
  4. DH Choi, "Analysis on Special Protection Scheme of Korea Electric Power System by Fully Utilizing STATCOM in a Generation Side", IEEE Transactions on Power Systems, Vol. PP, August 2016.