DOI QR코드

DOI QR Code

Study on Seismic Performance Evaluation and Verification of Seismic Safety for Power Cable Tunnels

개착식 전력구의 내진성능 평가 및 내진 안전성 검증

  • Received : 2019.12.26
  • Accepted : 2020.03.25
  • Published : 2020.12.30

Abstract

In this paper, the seismic performance evaluation was performed on 100 existing open-cut power cable tunnels, including ones that did not consider seismic design, in order to verify that the government's demand level (seismic special grade, 0.22 g). The results of the seismic performance evaluation show that most of the tunnels have seismic performance of 0.3 to 1 g, satisfying the level of the seismic special grade and securing the seismic safety. Meanwhile, the earthquake response analysis and structural test were performed to verify the validity of the method and the results of the seismic performance evaluation of the tunnels by the response displacement method, and to verify their seismic safety. As a result, the relative displacement due to the response displacement method under the 0.22 g earthquake was conservative than the results of the earthquake response analysis, and the results of load-displacement curves and response modification coefficient calculation by real scale structural tests showed the safety of the tunnels.

본 논문에서는 내진설계가 고려되어 있지 않은 전력구를 포함한 기설 개착식 전력구 100개소를 대상으로, 정부의 요구수준(내진 특등급, 0.22 g)을 만족하는지 확인하기 위하여 내진성능 평가를 수행하였다. 내진성능 평가 결과, 대상 전력구들은 대부분 0.3-1 g의 내진성능을 보유하고 있는 것으로 나타나, 내진 특등급 수준을 만족하였으며 내진안전성을 확보하고 있는 것으로 나타났다. 한편 응답변위법에 의한 전력구의 내진성능 평가 방법 및 결과에 대한 타당성을 확인하고, 전력구의 내진 안전성을 검증하기 위한 지진응답 해석 및 구조실험을 수행하였다. 그 결과 0.22 g 수준의 지진 하에서 응답변위법에 의한 상대변위는 지진응답 해석 결과보다 보수적이었으며, 실규모 구조실험에 의한 하중-변위 곡선 및 응답수정계수 산정 결과를 통해 전력구의 내진 안전성을 확인할 수 있었다.

Keywords

Acknowledgement

본 연구는 한국전력공사의 2016년 선정 주력연구개발과제연구비에 의해 지원되었음(과제번호: R16SA06).

References

  1. The Ministry of Land, Infrastructure & Transportation, "Design Criteria for Common Utility Tunnels," 2016.
  2. The Ministry of Land, Transport & Maritime Affairs, "Design Criteria for Concrete Structures," 2012.
  3. Korea Electric Power Corporation, "Seismic Design Guidelines for Transmission & Distribution Facilities," May 2014.
  4. The Ministry of Interior & Safety, "Common Application of Seismic Design Criteria," Apr. 2017.
  5. KEPCO Research Institute, "Study on Seismic Reinforcement Plans for Existing Transmission and Distribution Cable Tunnels and Electric Facilities around Yangsan Fault (TR 9346 S2019 0195)," pp. 3-150, Aug. 2019.
  6. Duhee Park, Jongho Shin, Seung Yun, "Seismic Analysis of Tunnels in Transverse Direction Part I: Estimation of Seismic Tunnel Response via Method of Seismic Displacement," Journal of the Korean Geotechnical Society, Vol. 26, No. 6, pp. 57-70, Jun. 2010.
  7. Yongmin Kim, Sangseom Jeong, Yonghee Lee, Jungbum Jang, "Seismic Design of Vertical Shaft using Response Displacement Method," Journal of the Korean Society of Civil Engineers, Vol. 30, No. 6C, pp. 241-253, Nov. 2010.
  8. Hojune Ann, Sanggeun Song, Daehong Min, Sangmi An, Jungsik Kong, "Experimental and Analytical Evaluation of the Seismic Performance of a Concrete Box Structure Strengthened with Pre-flexed Members," Journal of Computational Structural Engineering Institute of Korea, Vol. 29, No. 5, pp. 397-403, Oct. 2016. https://doi.org/10.7734/COSEIK.2016.29.5.397
  9. Choonghyun Kang, Jungwon Huh, Innjoon Park, Kyeongmin Hwang, Jungbum Jang, "A Simple Seismic Vulnerability Sorting Method for Electric Power Utility Tunnels," Journal of the Korea Institute for Structural Maintenance and Inspection, Vol. 22, No. 5, pp. 110-118, Sep. 2018. https://doi.org/10.11112/JKSMI.2018.22.5.110